APPROVED BLD BLD2025-0195+Structural_Analysis_or_Calculations+2.10.2025_8.48.33_AM+4753299General Structural Notes
CRITERIA
1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE
DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (2021
EDITION).
2. DESIGN LOADING CRITERIA:
EARTHQUAKE . . . ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE
LATERAL SYSTEM: LIGHT FRAMED SHEAR WALLS, Vs = 8.0 KIPS
SITE CLASS=D, Ss=128, Sds=100, S1=45, SD1=83, Cs=0.154
SDC D (DEFAULT), I e=1. 0, R=6. 5
3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS,
TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM THE CONTRACTORS
WORK. THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY OR
ACTUAL AND/OR DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS AT
THE SITE AND/OR FOR ANY HAZARDS RESULTING FROM THE ACTIONS OF ANY TRADE
CONTRACTOR. THE STRUCTURAL ENGINEER HAS NO DUTY TO INSPECT, SUPERVISE,
NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES TO THE OWNER,
CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT SITE.
4. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND
STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN
ACCORDANCE WITH THE PLANS. CONFORM TO ASCE 37-14 "DESIGN LOADS ON
STRUCTURES DURING CONSTRUCTION".
5. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE
CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO
DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO
REVIEW AND APPROVAL BY THE ARCHITECT AND THE STRUCTURAL ENGINEER. ALL
TYPICAL NOTES AND DETAILS SHOWN ON DRAWINGS SHALL APPLY, UNLESS NOTED
OTHERWISE. TYPICAL DETAILS MAY NOT NECESSARILY BE INDICATED ON THE PLANS
BUT SHALL STILL APPLY AS SHOWN OR DESCRIBED IN THE DETAILS. WHERE TYPICAL
DETAILS ARE NOTED ON THE PLANS, THE SPECIFIED TYPICAL DETAIL SHALL BE USED.
WHERE NO TYPICAL DETAIL IS NOTED, IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO CHOOSE THE APPROPRIATE TYPICAL DETAIL FROM THOSE
PROVIDED OR REQUEST ADDITIONAL INFORMATION. THE CONTRACTOR SHALL SUBMIT
ALL PROPOSED ALTERNATE TYPICAL DETAILS TO THOSE PROVIDED WITH RELATED
CALCULATIONS TO THE ENGINEER FOR APPROVAL PRIOR TO SHOP DRAWING PRODUCTION
AND FIELD USE.
RENOVATION
6. DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE
COMMENCING ANY DEMOLITION. SHORING SHALL BE INSTALLED TO SUPPORT EXISTING
CONSTRUCTION AS REQUIRED AND IN A MANNER SUITABLE TO THE WORK SEQUENCES.
DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING
STRUCTURE. LIMIT CONSTRUCTION LOADING (INCLUDING DEMOLITION DEBRIS) ON
EXISTING FLOOR SYSTEMS TO 40 PSF.
7. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND
CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING
CONSTRUCTION SHOWN ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND
MUST BE VERIFIED. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND STRUCTURAL
ENGINEER IF EXISTING CONDITIONS DETERMINED DURING WORK VARY FROM THE
EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS.
8. CONTRACTOR SHALL CHECK FOR DRY ROT AT ALL AREAS OF NEW WORK. ALL ROT
SHALL BE REMOVED AND DAMAGED MEMBERS SHALL BE REPLACED OR REPAIRED AS
DIRECTED BY THE STRUCTURAL ENGINEER OR ARCHITECT.
WOOD
9. FRAMING LUMBER SHALL BE S-DRY, KD, OR MC-19, AND GRADED AND MARKED IN
CONFORMANCE WITH WCLIB STANDARD No. 17, GRADING RULES FOR WEST COAST
LUMBER, 2018, OR WWPA STANDARD, WESTERN LUMBER GRADING RULES 2017.
FURNISH TO THE FOLLOWING MINIMUM STANDARDS:
ALL STRUCTURAL WOOD DOUGLAS-FIR-LARCH OR HEM -FIR NO. 2
10. PLYWOOD SHEATHING SHALL BE GRADE C-D, EXTERIOR GLUE OR STRUCTURAL II,
EXTERIOR GLUE IN CONFORMANCE WITH DOC PS 1 OR PS 2. ORIENTED STRAND BOARD
OF EQUIVALENT THICKNESS, EXPOSURE RATING AND PANEL INDEX MAY BE USED IN
LIEU OF PLYWOOD.
WALL SHEATHING SHALL BE 1/2" (NOMINAL) WITH SPAN RATING 24/0.
PROVIDE APPROVED PLYWOOD EDGE CLIPS CENTERED BETWEEN JOISTS/TRUSSES AT
UNBLOCKED ROOF SHEATHING EDGES. ALL FLOOR SHEATHING EDGES SHALL HAVE
APPROVED T&G JOINTS OR SHALL BE SUPPORTED WITH SOLID BLOCKING. ALLOW 1/8"
SPACING AT ALL PANEL EDGES AND ENDS OF FLOOR AND ROOF SHEATHING.
REFER TO WOOD FRAMING NOTES BELOW FOR TYPICAL NAILING REQUIREMENTS.
11. ALL WOOD IN DIRECT CONTACT WITH CONCRETE OR MASONRY SHALL BE
PRESSURE -TREATED WITH AN APPROVED PRESERVATIVE OR (2) LAYERS OF ASPHALT
IMPREGNATED BUILDING PAPER SHALL BE PROVIDED BETWEEN UNTREATED WOOD AND
CONCRETE OR MASONRY.
12. PRESERVATIVE TREATED WOOD SHALL BE TREATED PER AWPA STANDARD U1 TO THE USE
CATEGORY EQUAL TO OR HIGHER THAN THE INTENDED APPLICATION. TREATED WOOD
FOR ABOVE GROUND USE SHALL BE TREATED TO AWPA UC3B. WOOD IN CONTINUOUS
CONTACT WITH FRESH WATER OR SOIL SHALL BE TREATED TO AWPA UC4A. WOOD FOR
USE IN PERMANENT FOUNDATIONS SHALL BE TREATED TO AWPA UC4B.
13. FASTENERS AND TIMBER CONNECTORS USED WITH TREATED WOOD SHALL HAVE
CORROSION RESISTANCE AS INDICATED IN THE FOLLOWING TABLE, UNLESS OTHERWISE
NOTED.
WOOD TREATMENT CONDITION PROTECTION
HAS NO AMMONIA CARRIER INTERIOR DRY G90 GALVANIZED
CONTAINS AMMONIA CARRIER INTERIOR DRY G185 OR A185 HOT DIPPED OR
CONTINUOUS HOT -GALVANIZED
PER ASTM A653
CONTAINS AMMONIA CARRIER INTERIOR WET TYPE 304 OR 316 STAINLESS
CONTAINS AMMONIA CARRIER EXTERIOR TYPE 304 OR 316 STAINLESS
AZCA ANY TYPE 304 OR 316 STAINLESS
INTERIOR DRY CONDITIONS SHALL HAVE WOOD MOISTURE CONTENT LESS THAN 19%.
WOOD MOISTURE CONTENT IN OTHER CONDITIONS (INTERIOR WET, EXTERIOR WET, AND
EXTERIOR DRY) IS EXPECTED TO EXCEED 19%. CONNECTORS AND THEIR FASTENERS
SHALL BE THE SAME MATERIAL. COMPLY WITH THE TREATMENT MANUFACTURERS
RECOMMENDATIONS FOR PROTECTION OF METAL.
THE FOLLOWING APPLY UNLESS SHOWN OTHERWISE ON THE DRAWINGS
14. TIMBER CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -TIE"
BY SIMPSON COMPANY, AS SPECIFIED IN THEIR CATALOG NUMBER C-C-2019.
EQUIVALENT DEVICES BY OTHER MANUFACTURERS MAY BE SUBSTITUTED, PROVIDED
THEY HAVE ICC-ES APPROVAL FOR EQUAL OR GREATER LOAD CAPACITIES. PROVIDE
NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY MANUFACTURER FOR MAXIMUM LOAD
CARRYING CAPACITY. CONNECTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
ALL 2X JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "LUS" SERIES JOIST
HANGERS. ALL TJI JOISTS SHALL BE CONNECTED TO FLUSH BEAMS WITH "ITS"
SERIES JOIST HANGERS. ALL DOUBLE -JOIST BEAMS SHALL BE CONNECTED TO FLUSH
BEAMS WITH "MIT" SERIES JOIST HANGERS.
WHERE CONNECTOR STRAPS CONNECT TWO MEMBERS, PLACE ONE-HALF OF THE NAILS OR
BOLTS IN EACH MEMBER.
ALL SHIMS SHALL BE SEASONED AND DRIED AND THE SAME GRADE (MINIMUM)AS
MEMBERS CONNECTED.
15. WOOD FASTENERS
A. NAIL SIZES SPECIFIED ON DRAWINGS ARE BASED ON THE FOLLOWING
SPECIFICATIONS:
SIZE LENGTH DIAMETER
8d 2-1/2" 0. 131"
10d 3" 0. 148"
16d BOX 3-1/2" 0.135"
IF CONTRACTOR PROPOSES THE USE OF ALTERNATE NAILS, THEY SHALL SUBMIT
NAIL SPECIFICATIONS TO THE STRUCTURAL ENGINEER (PRIOR TO CONSTRUCTION)
FOR REVIEW AND APPROVAL.
NAILS - PLYWOOD (APA RATED SHEATHING) FASTENERS TO FRAMING SHALL BE
DRIVEN FLUSH TO FACE OF SHEATHING WITH NO COUNTERSINKING PERMITTED.
TOE -NAILS SHALL BE DRIVEN AT AN ANGLE OF 30 DEGREES WITH THE MEMBER AND
STARTED 1/3 THE LENGTH OF THE NAIL FROM THE MEMBER END.
B. ALL BOLTS IN WOOD MEMBERS SHALL CONFORM TO ASTM A307. PROVIDE WASHERS
UNDER THE HEADS AND NUTS OF ALL BOLTS AND LAG BOLTS BEARING ON WOOD.
INSTALLATION OF LAG BOLTS SHALL CONFORM TO THE NATIONAL DESIGN
SPECIFICATION FOR WOOD CONSTRUCTION WITH A LEAD BORE HOLE OF 60 TO 70
PERCENT OF THE SHANK DIAMETER. LEAD HOLES ARE NOT REQUIRED FOR 3/8"
AND SMALLER LAG SCREWS.
16. WOOD FRAMING NOTES --THE FOLLOWING APPLY UNLESS OTHERWISE SHOWN ON THE APPROVED
PLANS:
A. ALL WOOD FRAMING DETAILS NOT SHOWN OTHERWISE SHALL BE CONSTRUCTED TO PLANS MUST B
THE MINIMUM STANDARDS OF THE INTERNATIONAL BUILDING CODE, THE AITC
"TIMBER CONSTRUCTION MANUAL" AND THE AWC "NATIONAL DESIGN SPECIFICATION ON JOB SITE
FOR WOOD CONSTRUCTION". MINIMUM NAILING, UNLESS OTHERWISE NOTED, SHALL
CONFORM TO IBC TABLE 2304.10.1. COORDINATE THE SIZE AND LOCATION OF
ALL OPENINGS WITH MECHANICAL AND ARCHITECTURAL DRAWINGS.
B. WALL FRAMING: REFER ARCHITECTURAL DRAWINGS FOR THE SIZE OF ALL WALLS. ALL WORK SUBJECT
ALL STUDS SHALL BE SPACED AT 16" 0. C. UNO. TWO STUDS M I N I MUM SHALL BE
PROVIDED AT THE END OF ALL WALLS AND AT EACH SIDE OF ALL OPENINGS, AND
AT BEAM OR HEADER BEARING LOCATIONS. TWO 2x8 HEADERS SHALL BE PROVIDED TO FIELD
OVER ALL OPENINGS NOT OTHERWISE NOTED. SOLID BLOCKING FOR WOOD COLUMNS
SHALL BE PROVIDED THROUGH FLOORS TO SUPPORTS BELOW. PROVIDE CONTINUOUS INSPECTION F O R
SOLID BLOCKING AT MID -HEIGHT OF ALL STUD WALLS OVER 10'-0" IN HEIGHT.
ALL WALLS SHALL HAVE A SINGLE BOTTOM PLATE AND A DOUBLE TOP PLATE. END CODE COMPLIANCE
NAIL TOP PLATE TO EACH STUD WITH TWO 16d NAILS, AND TOENAIL OR END NAIL
EACH STUD TO BOTTOM PLATE WITH TWO 16d NAILS. FACE NAIL DOUBLE TOP
PLATE WITH 16d @ 12" 0. C. AND LAP MINIMUM 4'-0" AT JOINTS AND PROVIDE
EIGHT 16d NAILS @ 4" 0. C. EACH SIDE JOINT.
ALL STUD WALLS SHALL HAVE THEIR LOWER WOOD PLATES ATTACHED TO WOOD
FRAMING BELOW WITH TWO ROWS OF 16d NAILS @ 12" ON -CENTER, OR ATTACHED
TO CONCRETE BELOW WITH 5/8" DIAMETER ANCHOR BOLTS @ 4'-0" ON -CENTER
EMBEDDED 7" MINIMUM, UNLESS INDICATED OTHERWISE. INDIVIDUAL MEMBERS OF
BUILT-UP POSTS SHALL BE NAILED TO EACH OTHER WITH TWO ROWS OF 16d @12"
ON -CENTER. UNLESS OTHERWISE NOTED, GYPSUM WALLBOARD
TO THE INTERIOR SURFACE OF ALL STUDS AND PLATES WI
TYPE S OR W SCREWS @ 8" ON -CENTER. UNLESS INDICAT
(NOM I NAL) APA RATED SHEATHING ( SPAN RATING 24/0) SHALL
EXTERIOR SURFACES WITH 8d NAILS @ 6" ON -CENTER AT PA
AND BOTTOM PLATES (BLOCK UN -SUPPORTED EDGES)AND TO
STUDS AND BLOCKING WITH 8d NAILS @ 12" ON -CENTER ALL
ALL PANEL EDGES AND PANEL ENDS.
Special Inspection required for
retrofit epoxy anchors. Provide
reports to building inspector for
review.
itOf Edmonds
D OTHERWISE, 1 " y
DC A TI L-U IE-nV All
IY U/11 LLU /\LL
L 11
=L EDGES AND TOP Building Department
ALL 1N
W V#6rkPACING AT SEISMIC RETROFIT
Address 24206 89TH PL W
Owner DARLINGTON
Approved Date 02/19/2025
Building Official r( & C4**,r
1
Permit Number BLD2025-0195
O 1�
✓
I
N cm
d o
cm N
0 0
1
= 33 b
1A) OW
I
HDU2
1/S2.1,
N
1 /s2.1 310`%
1/S2.1,
N
o
r 16
o I
NJ
I cl I
W I �ppu1
Do C) 4- HDU2
1 /S2.1 ,
1 /S2.1
1 /S2.1
p p,l
1/S2.1
r
HDU2
S-rD���
4
(
9 HDU2
/-Ts'�-.tiij� I
r
h
WALLS
M
o
�
2
�
nl
3
-L
HDU2
,
HDU2
1/S2.1
:D>
t 2/S2.1 =
> �'
< 2/S2.1 4 1/S2.1
��� ��
HDU2
- -
V111 1IJ1 N
HDU2
I IIIOOt
O+.(
('t>,
Ca►.1'rII.,EdEr�EO po R CI-1
rJCr-)t4 -6AS~r Dkf Rif -I` OFI 1-
7- 4 2 6 '?9 n' PL vv,
CDmonlDS, w.A g160046
?>AgZeL -eOd5-11706000(00
�a6,4L t--S Cel r'>TI 01d : MA-TH AXIS
s l_ :Two 5a V#WLF-S
'- O N'a Foa
A r-)D 3 BLJL Qa o D O o LO"r f
Retrofit Plan
Scale: 1/4 11 = 1'-0"
4
AMERICAN SOCIETY OF CML ENGINEERS
Address:
24206 89th PI W
Edmonds, Washington
98026
ASCE Hazards Report
Standard: ASCE/SE17-16 Latitude: 47.77938
Risk Category: II Longitude:-122.353392
Soil Class: D - Default (see Elevation: 460.48003140858884 ft
Section 11.4.3) (NAVD 88)
r t
2351h St 'A
r
�
tJ
39th 51 SW
♦y
24atllsl sw.. _ ; •I
r1 ir >449-5, S11V
N 21411. St
vz
Aurora villa
Ni�.•.Ytibl � Vi16ae
ew
- l i
Seismic
Site Soil Class:
D - Default (see Section 11.4.3)
Results:
Ss :
1.278 Sol
N/A
S,
0.448 T L
6
Fa
1.2 PGA:
0.542
Fv
N/A PGA M :
0.65
SMs
1.533 FPC,A
1.2
SM1
N/A le
1
SIDS
1.022 Cv :
1.356
Ground motion hazard analysis may be required. See ASCE/SEI 7-16 Section 11.4.8.
Data Accessed:
Tue Jan 28 2025
Date Source:
USGS Seismic Desian Maps
b -rin
I r i�i
Seismic Retrofit (IBC 2021/ASCE 7-16)
Seismic Criteria:
OCCUPANCY CATEGORY: II NO. STORIES ABV. GR. 1
IMPORTANCE FACTOR: 1.0 Section 12.8.1.3 Exceptions
SITE CLASS D (Default)
SDS= 1.000
R = 6.5
SD1= 0.830
h = 19.5 ft
Period, T= 0.186
Sr, = 1.278
CS 0.154
S, = 0.448
Cemax= 0.688
Fa = 1.2
Cemil= 0.010
Ki'l1.-.1, F
Regular Structure-
Yes
<_ 5 Stories above grade
Yes
T 5 0.5s
Yes
p =1.0
Yes
Not Site Class E or F
Yes
Risk Category I or II
Yes
Fv = 1.85 Controlling CS 0.154 If all exceptions are met, Sos may be taken as 1, but not
less than 0.7'(Calculated Sos)
Building Weight "Regular Structure per Section 12.3.2
Floor
DL (psf)
A (sq.ft.)
W (Ibs)
Roof
20
1862
37240
2nd
20
1862
37240
Sum=
74480
Wall Seismic Loading:
Redundancy Factor, p = 1.0
Base Shear, VBASE = 11458 Ibs
VASD= •NBase = 8021 Ibs
Wall
V (Ibs)
Wall Ift)
v (Ibs/ft)
North Exterior
4010
14.0
286
South Exterior
4010
15.0
267
West Exterior
4010
20.5
196
East Exterior
4010
10.0
401
Sill Plate Bolting:
M
Wall
1/2" Dia Titen HD
URFP
FRFP
SIDS Option C Rim
North Exterior
32 in oc
48 in oc
48 in oc
16 in oc
South Exterior
32 in oc
48 in oc
48 in oc
16 in oc
West Exterior
48 in oc
72 in oc
72 in oc
16 in oc
East Exterior
16 in oc
32 in oc
32 in oc
16 in oc
Pony Wall Retrofit:
Wall
Hw (ft)
Edge Nailing
A35/11_70
I Uplift (Ibs)
Trib DL (Ibs)
Net Uplift (Ibs)
Holdown
Min. Lw w/o HD
North Exterior
6.75
8d04
16 in oc
1934
0
1934
HDU2
N/A
South Exterior
6.75
8dCd4
16 in oc
1805
0
1805
HDU2
N/A
West Exterior
6.75
8d@4
16 in oc
1321
0
1321
HDU2
N/A
East Exterior
6.75
8d@3
16 in oc
2707
0
2707
HDU2
N/A
ERING
2124 Third Avenue. Suite 100. Seattle. WA 98121
www.ssfengineers.com
Office: 206.443.6212
Fax: 206.443.4870
Date: 1/29/2025
Project #: 12169-2025-04
Design: JDT
Sheet: CR-1
L
\X�/ ENNEEMN
2124 Third Avenue - Suite too - Seattle, WA 98121
p:2o6.443.6212 ssfengineers.com
Copyright 2021 Swenson Say Faget - All Rights Reserved
DRAWN:
JDT
DESIGN:
JDT
CHECKED:
JDT
APPROVED:
GFJ
REVISIONS:
D�
RECEIVED
2/10/2025
CITY OF EDMONDS
DEVELOPMENT
SERVICES DEPARTMENT
PROJECT TITLE:
Darlington -Gaston Retrofit
24206 89th PI W
Edmonds, WA 98026
CLIENT:
Evergreen Seismic
21304 82nd Place Southeast
Snohomish, Washington 98290
IS
Permit
S' TITLE:
Retrofit Plan
SCALE:
N.T.S.
DATE:
January 29, 2025
PROJECT NO:
12169-2025-04
SHEET NO:
NO: OF SHEETS:
ASSUMED (E) NAILING
(E) WALL ABOVE
(E) JOISTS &SHEATHING
VERIFY (E) 2x RIM OR
FULL —DEPTH BLKG.
8d @ 4"oc OR PROVIDE
SDS1/4x6 SCREW @ 12"oc
PROVIDE 3/4" CDX PLYWOOD, (E) PONY WALL
BLOCK EDGES & NAIL W/ 8d
4"oc EDGES, 12"oc FIELD
(E) SILL PLATE W/ NEW HDU2—SDS2.5 W/
1/2" 0 TITEN HD CONC. SCREWS (6)SDS'/4x2l/2 SCREWS
32"oc (31/2" conc. embed) TO DOUBLE STUDS
(where occurs)
EPDXY GROUT 5/8" 0 THREADED
ROD 8"(min.) INTO (E) CONCRETEII; PROVIDE 1/4"x3"x3" STEEL
NEW HD LOCATIONS INSTALL
2 INSTALL
3/4 lullPLATE WASHER @NEW SILL
A SLIGHT ANGLE TO
PLATE ANCHORAGE
EDGE DISTANCE min.
a
(E) FOUNDATION WALL
a
Retrofit Detail
ASSUMED (E) NAILING
(E) WALL ABOVE
(E) JOISTS &SHEATHING
VERIFY (E) 2x RIM OR
FULL —DEPTH BLKG.
8d @ 3"oc OR PROVIDE
SDS1/4x6 SCREW @ Toc *571
PROVIDE 3/4" CDX PLYWOOD, (E) PONY WALL
BLOCK EDGES & NAIL W/ 8d
3"oc EDGES, 12"oc FIELD
(E) SILL PLATE W/ NEW HDU2—SDS2.5 W/
1/2" 0 TITEN HD CONC. SCREWS (6)SDS'/4x2l/2 SCREWS
16"oc (31/2" conc. embed) � � TO DOUBLE STUDS
(where occurs)
EPDXY GROUT 5/8" 0 THREADED
ROD 8"(min.) INTO (E) CONCRETEII; PROVIDE 1/4"x3"0" STEEL
@ NEW HD LOCATIONS, INSTALL 23/4„ �u; PLATE WASHER @ NEW SILL
SLIGHT ANGLE TO ACHIEVE PLATE ANCHORAGE
EDGE DISTANCE min. °
(E) FOUNDATION WALL
Retrofit Detail 2
L
Nlx�/ ENNEEMN
2124 Third Avenue - Suite loo - Seattle, WA 98121
p:2o6.443.6212 ssfengineers.com
Copyright 2021 Swenson Say Faget - All Rights Reserved
DRAWN:
JDT
DESIGN:
JDT
CHECKED:
JDT
APPROVED:
GFJ
REVISIONS:
D�
RECEIVED
2/10/2025
CITY OF EDMONDS
DEVELOPMENT
CERVICES DEPARTMENT
PROJECT TITLE:
Darlington -Gaston Retrofit
24206 89th PI W
Edmonds, WA 98026
CLIENT:
Evergreen Seismic
21304 82nd Place Southeast
Snohomish, Washington 98290
ISSUE:
Permit
SHEET TITLE:
Retrofit Details
SCALE:
N.T.S.
DATE:
January 29, 2025
PROJECT NO:
12169-2025-04
SHEET NO:
S2,01
NO: OF SHEETS: