FIR2025-0033_Fire_Alarm_Battery_Calculations_3.20.2025_11.14.43_AM_4821446
GUARDIAN SECURITY Seattle - Tacoma - Poulsbo - Bellingham 1743 First Avenue South Seattle, WA 98134 Tel: 206.622.6545 Fax 206.341.9928 LCNW EDMONDS MEDICAL PLAZA SUITE 207 21616 76TH AVENUE WEST EDMONDS, WA. 98026 Fire Alarm System Submittals Proiect # 75514-1 BRAND MODEL# SIEMENS 0OH941 SIEMENS H1921 SIEMENS DB-11 BASE SIEMENS PC2RLED DESCRIPTION Dual Optical / Smoke and Heat Detector Heat Detector Detector Base Horn/Strobe Ceiling Intelligent Detection Devices Multi -Criteria Fire Detector [with ASAtechnologyTM] Model 0OH941 ARCHITECT AND ENGINEER SPECIFICATIONS • Advanced multi -criteria fire detector that has dual -optical and thermal sensors • Differentiates between deceptive phenomena and an actual fire (nuisance -alarm avoidance) • Compatible with Siemens Model'H'-series devices on the same loop (with Cerberus PRO fire -alarm control panels [FACPs] or FireFindero XLS FACPs) • Provides enhanced detection via forward -and -backward light -scattering technology • Complies with NFPA 76 (Telco standard) as'VEWFD' high -sensitivity detector • OUL Listed and FM Approved as a multi -criteria and 'VEWFD' fire detector • oUL 268A Listed for direct air -duct (4,000 FPM) use • Supervisory temperature -monitoring feature • Remote sensitivity -measurement capability 4L • Automatic environment compensation - • Up to 22 application profiles • Tri-color detector status LED with 360' viewing • Environmental alternative to ionization detectors • Polarity insensitive utilizing SureWireTM technology • Low -temperature warning for sprinkler systems, per NFPA 25 • Meets OUL, NFPA 72 requirements for sensitivity self -monitoring • Compatible with: • Legacy Model DB-11—series mounting bases ®UL 268 compliant • Model 87201 DPU (device programmer 1 loop tester) • Restriction of Hazardous Substances (RoHS) compliant OUL Listed and ULC Listed; • Responds to both flaming and smoldering -fire signatures FM and CSFM Approved Product Overview Model OOH941 is an advanced, multi -criteria fire detector that incorporates a redundant, optical 1 thermal sensor. Model OOH941 uses a distinctive forward I backward, light -scattering technology that provides state-of-the-art, unparalleled fire detection to the widest range of fire types. Model OOH941 is programmable as a high -sensitivity detector, meeting the requirements of NFPA 76 Standard (for the Fire Protection of Telecommunications Facilities) as a Very Early Warning Fire Detector (VEWFD). CerberuSTM PRO Fire Safety & Security Products Answers for infrastructure The Model OOH941 detector is a flexible, multi -purpose detector that provides a complete solution to meet detection needs. This type of detector can be field programmed for simultaneous and 1 or independent functionality, depending upon the exact customer and application requirements. For example, the detector can simultaneously utilize the optical and heat sensors for enhanced fire detection (multi -criteria), as well as provide together independent outputs for heat detection. Any combination of the sensors is possible. The detector is extremely versatile and meets the following standards: Multi -Criteria Fire Detector [with ASAtechnologyTm] SIEMENS Product Overview — (continued) • Multi -criteria fire detector ((WL 268) • Heat detector (oUL 521) with five (5) possible field -selectable temperatures; combined with four (4) rate -of -rise options • Direct, in -duct (plenum) detector (oUL 268A) • Supervisory monitoring for temperature ranges • NFPA 76 (Telco Standard) as VEWFD • Low -temperature warning signal at 40°F (4.4°C) — for sprinkler systems, per NFPA 25 I NFPA 72 Model 0OH941 —which provides extremely accurate and reliable fire detection with built-in redundancy— utilizes advanced, multi -criteria detection technology known as ASA (Advanced Signal Analysis) that allows the detector to distinguish non -threatening deceptive phenomena. For instance, the signals from the detector's sensors are monitored and processed via the ASA-patented algorithm technology, which combines the signals into a neural network to create an intelligent, multi -criteria detector. The encompassing result is a detector that provides enhanced detection to a wide range of products of combustion —while offering unsurpassed rejection to nuisance -alarm sources, such as: dust, steam, aerosols and other deceptive phenomena that could cause false alarms. Since Model 0OH941 is a (2) two -wire, addressable device, it is able to function as a multi -purpose detector — satisfying smoke and heat detection in a singular, aesthetically pleasing package. Further, Model 0OH941 serves as an extremely cost-effective, viable solution that saves product, installation and maintenance costs (compared to other multiple -detector alternatives). Each detector fits into one (1) wall -or -ceiling footprint, and only occupies one (1) address on the signal -line circuit (SLQ. A patented forward -and -backward, light -scattering technology —which is able to distinguish both small and large products of combustion — operates at the core of each Model 0OH941 detector. Additionally, each Model 0OH941 provides an environmental -friendly solution to ionization detectors, eliminating the need for a radioactive source and eventual disposal requirements. Thus, each detector is capable of detecting both smoldering and flaming fire —all in ecologically efficient manner —and is a valid, RoHS- compliant (Restriction of Hazardous Substances) detection alternative to ionization detectors. Two (2) thermal sensors make each Model 0OH941 detector a robust, reliable device suitable for the most challenging applications. SIEMENS Industry, Inc. Building Technologies Division Operation Forward -and -Backward Light -Scattering Technology 1. Heat sensors 2. Receiver 3. Backward scatterer 4. Forward scatterer 5. Labyrinth The high -quality, optical -electronic measuring chamber for each Model 0OH941 houses the following components: ✓ Two (2) optical transmitters ✓ One (1) optical receiver ✓ Two (2) thermal sensors The transmitters illuminate the smoke particles from different angles: one sensor acts as forward scatterer, the other sensor as a backward scatterer. The scattered light then hits the receiver (photodiode) and generates a measurable electric signal. The combination of a forward -and -backward scatterer facilitates optimum detection, as well as differentiates between light -and -dark particles 1 particle size. This type of detection creates standardized, responsive behavior, thus optimizing the differentiation between wanted signals and deceptive phenomena. In addition, the heat sensors make it possible to detect fires without smoke generation. This scenario generates the following advantages: ✓ Early detection of all fire types of fire —whether they generate light -or -dark smoke, or no smoke ✓ The fire detector can be operated at a lower sensitivity level, thus achieving a higher immunity against false alarms that may otherwise be caused by cold aerosols (e.g. — by smoking, electrical welding, etc.). In the case of an open fire, the smoke sensitivity is heightened by a temperature increase —which means that a detection -reliability level that is comparable to a wide -spectrum smoke detector — can be achieved and maintained. Note: For Model 0OH941 compatibility to FireFinder® XLS, the XLS FACP requires Model PMI-2 (no firmware upgrade required), or Model PMI (firmware Rev. 9 or higher is required). The detector's compatibility also requires both of following: - Rev. 9 (or higher) ZEUS custom -configuration software - Rev. 6 (or higher) Device Loop Card (DLC) firmware CerberusTM PRO Operation — (continued) Field -Device Programmer / Test Unit Model 0OH941 is compatible with the Device Program 1 Test Unit accessory, which is used to program and verify the address of the detector. The technician selects the accessory's program mode, and enters the desired address. Model 87201 DPU automatically sets and verifies the address and tests the detector. Model 8720 / DPU eliminates the need for cumbersome, unreliable mechanical programming methods— such as dials or switches — and reduces installation and service costs by electronically programming and testing the detector prior to installation. Model 8720 / DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programmer and testing equipment from practically any location. When in'test' mode, Model 8720 / DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly. Field -selectable application profiles Model 0OH941 provides 22 user-friendly, field -selectable application profiles, indentified with universally known names (e.g. — Hotel, Telco, Office, Parking Garage, Dormitory, and Data Centeretc.) Referto installation manual: P/N— A6v10324655 for a complete list and description of application profiles. Due to generic -name classification, no cross-reference tables are required as the application name resides in the panel's configuration tool. This user-friendly feature— along with the algorithms provided byASAtechnology— provides a reliable, field -configurable detector suitable for an array of applications. Field -selectable temperature settings Model 0OH941 provides five (5) field -selectable temperature thresholds, ranging from 1350F to 175T (57°C to 79°C), with fixed and rate -of -rise options. These ranges provide maximum flexibility to program and to easily adjust the temperature settings that suit multi -application needs within a building or changing environmental conditions. Additionally, Model 0OH941 can be configured to provide a low -temperature warning signal at 40T (4.4°C). This configuration (along with connection to a compatible fire alarm control panel {FACP}) meets NFPA 72 requirements for sprinkler -temperature monitoring, and serves as prevention of water freezing in pipes for water -based suppression systems. SIEMENS Industry, Inc. Building Technologies Division Ambient supervisory feature for temperature -threshold ranges Another highlight for Model 0OH941 is supervision of ambient temperatures, allowing the end user to set an unique, specified warning point at a customized temperature threshold ranging from -47 to 120°F (-20°C to 49 °C). This feature is practical for monitoring of machinery; special processes, or for environments where maintaining a temperature is critical as an early -warning supervisory signal. Self -monitoring for smoke -sensor sensitivity Model 0OH941 provides an automatic self -monitoring sensitivity check that complies with the NFPA 72 sensitivity requirements. When connected with a compatible FACP, it provides automatic and dynamic sensitivity verification within the agency -listed -and -approved limits. Besides checking for sensor integrity and automatic environmental compensation, Model 0OH941 provides a display and report of sensitivity in percent -per -foot (or percent -per -meter) at the FACP. Profile Overview The Model 0OH941 detector contains a tri-color LED indicator, capable of flashing anyone (1) of three (3) distinct colors: green, or red. During each flash interval, the microprocessor -based detector monitors the following: • Smoke in its sensing chamber • Smoke sensitivity is within the range indicated on the nameplate label • Internal sensors and electronics Based on the results of the monitoring, the LED indicator flashes the following: Flash Flash Condition Interval Color (in seconds) Normal supervisory operation. Green*: Smoke sensitivity is within rated 10 limits. Yellow: Detector is in trouble and needs 4 replacement. Red: Alarm condition. 1 No Flash: Detector is not powered. -- * LED can be turned OFF. Please follow the corresponding description of the panel used. A quick, visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from each Cerberus PRO FACP, indicating the status and settings assigned to each individual detector. CerberusTM PRO Installation All Model 0OH941 detectors use a surface -mounting base (Model DB-11 or Model DB-11 E), which mounts on a 4-inch octagonal, square or single -gang electrical box. The base utilizes screw -clamp contacts for electrical connections and self -wiping contacts for increased reliability. The Model DB-11 base can be used with the optional Model LK 11 detector locking kit, which contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has decorative plugs to cover the outer mounting screw holes. Model 0OH941 may be installed on the same initiating circuit with the Siemens Model'H'-series detectors [when used with Cerberus PRO FACPs] — • Models HFP-11, HFPT-11 • Model'HMS'-series manual stations • Model'HTRI'-series interfaces • Model HCP output -control devices • Model 'HZM'-series of addressable, conventional zone modules Each detector consists of the following: • Dust -resistant photoelectric chamber • Solid state, non -mechanical thermal sensor • Microprocessor -based electronics with a low -profile plastic housing Each Model 0OH941 fire detector is shipped with a protective dust cover: 2 1) Ma31 00X941 detector / � • 1 2) Dust 07OeT / (provided ^..pith eat detector) All Model 0OH941 detectors are approved for operation within the OUL-specified temperature range of 32' to 120°F (0' to 49°C) — depending on heat -detector configuration (see to installation manual: PIN A6V1 0324655) for details. Application Data Installation of Model 0OH941 detectors requires a two - wire circuit. In many retrofit cases, existing wiring may be used. 'T-tapping' is permitted only for Style 4 (Class B) wiring. Model 0OH941 is polarity insensitive, which can greatly reduce installation and debugging time. SIEMENS Industry, Inc. Building Technologies Division Model 0OH941 fire detectors can be applied within the maximum 30-feet center spacing (900 sq. ft. areas,) as referenced in NFPA 72. This application guideline is based on ideal conditions —specifically, smooth ceiling surfaces; minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire -protection - system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens — Fire Safety distributor or sales office whenever you need assistance applying Model 0OH941 in unusual applications. Be sure to follow NFPA guidelines and OUL Listed / ULC Listed installation instructions — included with every Siemens — Fire Safety detector —and local codes as for all fire protection equipment. Technical Data Operating Temperatures: +32°F (0°C) to 120°F (49°C) depending upon heat -detector configurations (see to installation manual: P/N A6V10324655) for details Heat -Detector Range: +135°F (57°C) to 17YF (79°C) Thermal Rating: 00H941 Selectable Temp. Profiles Fixed temperature 135)F Fixed temperature 1451F Fixed temperature 1550F Fixed temperature 1650F Fixed temperature 1750F Fixed temperature 135°F + Rate of Rise (RoR) 15OF Fixed temperature 1751F + Rate of Rise (RoR) 151F Fixed temperature 1350F + Rate of Rise (RoR) 201F Fixed temperature 1751F + Rate of Rise (RoR) 201F Selectable Alarm Threshold Setting Profiles 2.50 % / ft.Threshold 3.00 % / ft.Threshold 2.50 % ! ft.Threshold, verified 3.00 %,' ft.Threshold, verified CerberusTM PRO Technical Data — (continued) Detector Sensitivity Range: OUL: 0.77% to 3.82% I ft. NFPA 76 (Telco) VEWFD: 0.2% 1 ft. Pre -alarm, 1.0% I ft. Alarm Application Profiles: 22 (field configurable) Programmable Supervisory Temperature Warning available with compatible FACPs: -4°F (-20°C) to 120°F (49°C) Relative Humidity: 0-95%; non -condensing Air Velocity — (Open Area): 0 - 4,000 feet -per -minute (fpm) Direct -in -Duct: 0 - 4,000 (fpm) Air Pressure: No effect Maximum Spacing: 30-foot centers (900 sq. ft.), per NFPA 72 and ULC-S524 Listed Input Voltage Range: 13VDC - 32VDC Alarm Current: 650pA, max. Quiescent (Standby) Current: 280pA - 360pA Detector Weight: 0.281 lbs. (0.128 kg.) Approvals / Standards: FM 3210, 3220 CSFM 7272-0067:0260 oUL 268 NFPA 25 ©UL 268A NFPA 72 (DUL 521 NFPA 76 ULC-S524 Listed SIEMENS Industry, Inc. Building Technologies Division Mounting Diagrams Dimensions 4.1- (10.4 cm.) e� ,.s.. Model 0OH941 6.1" (15.5 cm.) , .s.. Model 0OH941 with Model DB-11 base (11.7cm.) 0 T Model 0OH941 with Model DB-11 E base Detector Compatibility Table Data Model Number Sheet Description Number — 6300 FireFinder0 XLS (system overview) DLC 6312 Device Loop Card 50-point panel MIT] 252-point system (networkable) 504-point system (networkable) CerberusTM PRO Details for Ordering Model Number Part Number Description 0OH941 S54320-F7-A2 Multi -Criteria Fire Detector with ASAtechnolo TM DB-11 500-094151 Detector Mounting Base DB-11 E 500-094151 E Detector Base {small) DB2-HR I S54320-F12-A1 Detector Mounting Base with Relay RL-HC 500-033230 Remote Alarm Indicator: 4" octagon -box mount, red RL-HW 500-033310 Remote Alarm Indicator: single -gang box mount, red LK-11 500-695350 Base Locking Kit In Canada, order: Model Part I Number Description Number DB-11 C 500-095687 1 Detector Mounting Base for ULC (Listed) SIEMENS CerberuSTM PRO Siemens Industry, Inc. — Building Technologies Div 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO Building Technologies Division SII —Fire Safety [Printed in U.S.A ] NOTICE —The information contained in this data -sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information. Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer. Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer. March 2013 — Supersedes sheet dated 2/2013 ( Rev. 2 ) SIEMENS ❑ Built-in ISOtechnologyTm The Intelligent Thermal (Heat) Detector (Model HI921) provides an advanced method of detection, address programming supervision - combined with sophisticated FACP ❑ Compatible with Siemens Model w ith series devices on the same loop (with communication. Model HI921 uses a state-of-the-art thermistor, microprocessor and Cerberus PRO Modular I FireFinder advanced signal analysis, providing high reliability and accuracy. XLS/V I FC9-series fire -alarm control Additionally, Each Model HI921 unit is UL listed including advanced built-in panels) ISOtechnologyTm - a "True Class-X" SLC operation (use is optional) greatly improving ❑ Contains seven (7) field -selectable system reliability and circuit integrity while providing advanced addressable fault settings in a temperature range of finding. 135°F - 175°F (57.2°C - 78.9°C) Each model HI921 is a cost-effective, intelligent, addressable thermal detector that ❑ Provides s low temperature warning provides distinctive, advanced features: seven (7) field -selectable temperature settings of 4o°F (4.4°C) specially tailored for application -specific detection needs combined with Class-X SLC ❑ Field programmable as rate -of -rise operation built-in avoiding additional installation and material cost. or fixed temperature The temperature -range settings for each Model HI921 detector is between 135°F (57°C) - ❑ Tri-color detector -status light -emitting 175°F (79°C) with fixed and rate -of -rise programmability. This variance provides the diode (LED) with 360 'view customer with maximum flexibility to program the temperature settings to suit multiple ❑ Compatible with Model 8720 1 DPU application needs and changing environmental conditions. (device programmer/ loop tester) Model HI921 can be configured to provide a low -temperature warning signal at 40°F ❑ Utilizes advanced, microprocessor- (4.4°C). This feature - along with a compatible FACP (Cerberus PRO Modular I FireFinder based signal processing XLSIV or with Cerberus PRO FC/FV922 or FC/FV924 FACPs) - serves as prevention of ❑ Each detector is self -testing: water freezing in pipes for sprinkler systems, meeting NFPA 72 - complete diagnostics Operation performed every 10 seconds ❑ Polarity insensitive via Model HI921 also utilizes a modern, accurate and shock -resistant thermistor to sense SureWireTm technology significant changes in temperature. ❑ Functions with Model DB- Each Model HI921 detector has seven (7) pre-programmed parameter sets that can be 11-series mounting bases selected by the Siemens FRCP. ❑ Superior electromagnetic interference (EMI) and radio -frequency interference (RFI) immunity ❑ Restriction of Hazardous Substances (RoHS compliant) ❑ UL 521 Listed, ULC Listed ❑ CSFM (#7272-0067:0258) Approved Thermal (Heat) Detector sFM Siemens Smart Infrastructure - Building Products Data Sheet9901 usa.siemens.com/fire 1. Thermistor NOTE: Each detector consists of a dust - resistant chamber, a solid state, functional internal sensor, and microprocessor -based electronics with a low -profile plastic housing. Thermal (Heat) Detector Model HI921 contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct colors: GREEN YELLOW I RED. During each flash interval, the microprocessor -based detector monitors the following fire -system conditions: Temperatures reaching programmed thresholds Internal sensors and electronics are functional Based on the results of the monitoring, the LED indicator flashes the following: FLASH COLOR CONDITION FLASH INTERVAL [in seconds] Normal supervisory operation. GREEN*: Temperature has not reached programmed 10 alarm thresholds or set points. YELLOW: Detector is not operating at 4 normal capacity and needs replacement. Alarm' condition 1 NO FLASH: Detector is not powered. — * denotes LED can be turned OFF Please follow the corresponding description of the panel used. A quick visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from the respective Cerberus PRO Modular FireFinder XLSIV or Model FC9-series FACPs that indicates the status and settings assigned to each detector. All Model HI921 detectors use a surface -mounting base, Model DB2-HR I DB-11 or Model DB-11 E, which mounts on a 4-inch (10.2 cm.) octagonal, square or single -gang electrical box. The base utilizes screw -clamp contacts for electrical connections and self -wiping contacts for increased reliability. The Model DB-1 1 detector base can be used with the optional Siemens Model LK-11 detector locking kit, which contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has aesthetically conducive plugs to cover the outer mounting -screw holes. Model HI921 may be installed on the same initiating circuit with the Siemens Model 'H'-series detectors and devices [when used with Cerberus PRO Modular I Model FC9-series I FireFinder XLSIV FACPs] — • HFP-11, HFPT-11 • Model 'XTRI'-series interfaces • Model 'XMS'-series manual stations • Model'HTRI'-series interfaces • Model 'HMS' -series manual stations • Model HCP output -control detection devices • Model 'HZM'-series of addressable, conventional zone modules Siemens usa.siemens.comlfire Smart Infrastructure - Building Products —2— Installation of Model HI921 intelligent, addressable thermal detector requires a two -wire SLC circuit. In many retrofit cases, existing wiring may be used. 'T-tapping' is permitted only for Style 4 (Class B) wiring. Model HI921 is polarity insensitive when not used in Class-X mode, which can reduce installation and debugging times. The unit's value is multiplied with built-in ISOtechnology the True Class-X - NFPA 72 compliant SLC isolation feature supporting up to 252 isolation ready devices per loop. When used in mixed mode a maximum of 30 non -isolated devices between isolation devices (wired in polarity -insensitive mode). Each detector fits into one (1) wall -or -ceiling footprint, and only occupies one (1) address on the signal -line circuit (SLC). Model HI921 can be applied within the maximum 50-feet (15.24 m.) center spacing (2,500 sq. ft. [232.3 sq. mJ) per Underwriters' Laboratories. This application guide is based on ideal conditions, specifically, smooth -ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not mount detectors in close proximity to heating I ventilation I air-conditioning (HVAC) outlets. Exposed joists or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire -protection system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens - Fire Safety distributor or sales office whenever you need assistance applying Model HI921 in unusual applications. Be sure to follow NFPA guidelines and UL Listed I ULC Listed installation instructions - included with every Siemens - Fire Safety detector - and local codes for all fire -protection equipment. Specificationsi Model HI921 is a plug-in, (2) two -wire thermal (heat) detector, compatible with Cerberus PRO Modular I FireFinder XLSIV and Model FC9-series FACPs. Each Model HI921 detector has microcomputer -chip technology and highly stable, solid-state electronic circuitry. Model HI921 detectors utilize a modern, accurate and shock -resistant thermistor to sense temperature changes. This electronic -sensing method virtually eliminates thermal lag associated with mechanical temperature -sensing devices and provides almost instantaneous temperature status to the FACP. Model HI921 provides seven (7) field -selectable, pre-programmed temperature settings: Fixed Temperature set points (5) Rate of Rise set points (2) • Fixed 135°F (57°C) • Fixed 145°F (63°C) • Rate -of -Rise: 15°F I min. (8.3°C) at fixed 135°F (57°C) • Fixed 155°F (68°C) • Rate -of -Rise: 15°F I min. (8.3°C) at fixed 175°F (79°C)— — — • Fixed 165°F (74°C) • Fixed 175°F (79°C) Additionally, the Model HI921 detector has the following optional feature: • Model HI921 provides indication of potential water freezing for sprinkler systems, via configuration for reporting a low -temperature warning of 407 (4.4°C). This feature is compatible with Cerberus PRO Modular systems, as well as with FireFinder XLSIV and Cerberus PRO FCIFV922 or FCIFV924 FACPs. ---- 4.1" (1 0.5 cm-) (4.9 CM. M 1.46" 3.7tm. M Model HI921 Siemens Smart Infrastructure - Building Products -3- usa.siemens.comlfire Model HI921 is compatible with the Siemens field -device programmer / test unit (Model 8720 1 DPU), which is a compact, portable and menu -driven accessory for electronically programming and testing these addressable detectors promptly and reliably. For instance, the field technician selects the accessory's program mode, and enters the desired address. Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods (e.g. — dials and rotary switches), and reduces installation and service costs by electronically programming and testing the detector prior to installation. When set in 'test' mode, Model DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly. Each field -device programmer / test unit operates on AC power or rechargeable batteries, providing flexibility and convenience in the programming / testing of fire -safety equipment from practically any location. Additionally, with the use of a Model DPU unit, there is no longer a cause for concern with any vibration, corrosion and other deteriorating conditions that can accompany the vitality of a mechanical -addressing mechanism. The encompassing result is an intelligent detector that provides enhanced detection capability to a wide range of products of combustion — while offering unsurpassed rejection to nuisance -alarm sources, including: dust I steam I aerosols and other deceptive phenomena that could cause false alarms. 132' — *1207 (0' — *49°C) [with 145°F (63°C) 1155°F (68°C) OPERATING 1165°F (WC) and 175°F (79°C) TEMPERATURE: alarm -threshold settings] '32° — *1007, (0° — *38oC) [ with 135°F (57°C) alarm threshold setting] Model H1921 provides seven (7) field -selectable, pre- programmed temperature settings: • Fixed 135°F (57°C) • Fixed 1457 (63°C) • Fixed 155°F (68°C) THERMAL • Fixed 165°F (74°C) RATING: • Fixed 1757 (79°C) • Rate -of -Rise: 157 / min. (8.3°C) at fixed 135°F (57°C) • Rate -of -Rise: 15°F/ min.(8.3°C) at fixed 175GF (79°C) RELATIVE 0 — 95% HUMIDITY: (non -condensing) AIR PRESSURE: No effect INPUT VOLTAGE 16VDC — 30VDC RANGE: -ALARM' 41 OpA CURRENT, MAX.: STANDBY' 250NA CURRENT, MAX.: MAXIMUM 50—ft. (15.24 m.) centers SPACING: (2500 sq. ft. 1232.3 sq. m.), per NFPA 72 and ULC-S524 DETECTOR WEIGHT: 0.317 Lbs. (0.144 kg.) Panel Compatibilities XLS 6300 FireFinder (fire) XLSV 6340 FireFinder (fire w/ voice) Cerberus PRO 8300 Cerberus PRO Modular 2500-point Modular addressable (fire & fire with voice) Cerberus PRO FC901 9813 50-point addressable Cerberus PRO FC922 252-pt. addressable (fire) 9815 Cerberus PRO FC924 504-pt. addressable (fire) Cerberus PRO 252-point addressable FV922 (fire w/ Intelligent Voice Communication 9821 [IVC]) Cerberus PRO 504-pt. addressable FV924 (fire w/ Intelligent Voice Communication [IVC]) MODEL ORTYPE PART NUMBER PRODUCT W IF Compatible Devices: MODEL PART PRODUCT OR TYPE NUMBER Buzzer Version ABHW4B S54320-F13-A1 Audible Base (standard 3,000 Hz tone) ABHWdBZ S54320 F13 A2 Audible Base Sleeping Room Version , ABHW�S S54320 F14 41 520 Hz Low Frequency Audible Base ABHW-0SZ S54320-F14-A2 Audible Base ADB-BOX 500-698360 Surface Mount Adapter Box for Audible Base Relay base compatible DB2-HR S54370 F12-A1 with Siemens standard and advanced detectors Detector DB-11 500 094151 Mounting Base DB 11E 500-094151E Detector Base, small Remote Alarm Indicator: RL-HC 500-033230 4" (10.2 cm) octagon -box mount, red Remote Alarm Indicator: RL-HW 500-033310 single -gang box mount, red LK-11 500-695350 Base Locking Kit See: www.STI-USA.com for further details on ordering Model STI-9604 In Canada order: MODEL PART 11 PRODUCT OR TYPE NUMBER Detector DB-11C 500-095687 Mounting Base, ULC Listed Siemens Smart Infrastructure - Building Products —4— usa.siemens.com/fire NOTICE— The information contained in this data -sheet document is intended only as a summary, and is subject to change without notice. The product(s) described here has/have a specific instruction sheet(s) that cover various technical, limitation and liability information. Copies of install -type, instruction sheets —as well as the General Product Warning and Limitations document, which also contains important data, are provided with the product, and are available from the Manufacturer. Data contained in the aforesaid type of documentation should be consulted with a fire -safety professional before specifying or using the product. Any further questions or assistance concerning particular problems that might arise, relative to the proper functioning of the equipment, please contact the Manufacturer. SIEMENS Intelligent Detection Devices Multi -Criteria Fire Detector [with ASAtechnologyTM] Model 0OH941 ARCHITECT AND ENGINEER SPECIFICATIONS • Advanced multi -criteria fire detector that has dual -optical and thermal sensors • Differentiates between deceptive phenomena and an actual fire (nuisance -alarm avoidance) • Compatible with Siemens Model'H'-series devices on the same loop (with Cerberus PRO fire -alarm control panels [FACPs] or FireFindero XLS FACPs) • Provides enhanced detection via forward -and -backward light -scattering technology • Complies with NFPA 76 (Telco standard) as'VEWFD' high -sensitivity detector • OUL Listed and FM Approved as a multi -criteria and 'VEWFD' fire detector • oUL 268A Listed for direct air -duct (4,000 FPM) use • Supervisory temperature -monitoring feature • Remote sensitivity -measurement capability 4L • Automatic environment compensation - • Up to 22 application profiles • Tri-color detector status LED with 360' viewing • Environmental alternative to ionization detectors • Polarity insensitive utilizing SureWireTM technology • Low -temperature warning for sprinkler systems, per NFPA 25 • Meets OUL, NFPA 72 requirements for sensitivity self -monitoring • Compatible with: • Legacy Model DB-11—series mounting bases ®UL 268 compliant • Model 87201 DPU (device programmer 1 loop tester) • Restriction of Hazardous Substances (RoHS) compliant OUL Listed and ULC Listed; • Responds to both flaming and smoldering -fire signatures FM and CSFM Approved Product Overview Model OOH941 is an advanced, multi -criteria fire detector that incorporates a redundant, optical 1 thermal sensor. Model OOH941 uses a distinctive forward I backward, light -scattering technology that provides state-of-the-art, unparalleled fire detection to the widest range of fire types. Model OOH941 is programmable as a high -sensitivity detector, meeting the requirements of NFPA 76 Standard (for the Fire Protection of Telecommunications Facilities) as a Very Early Warning Fire Detector (VEWFD). CerberuSTM PRO Fire Safety & Security Products Answers for infrastructure The Model OOH941 detector is a flexible, multi -purpose detector that provides a complete solution to meet detection needs. This type of detector can be field programmed for simultaneous and 1 or independent functionality, depending upon the exact customer and application requirements. For example, the detector can simultaneously utilize the optical and heat sensors for enhanced fire detection (multi -criteria), as well as provide together independent outputs for heat detection. Any combination of the sensors is possible. The detector is extremely versatile and meets the following standards: Multi -Criteria Fire Detector [with ASAtechnologyTm] SIEMENS Product Overview — (continued) • Multi -criteria fire detector ((WL 268) • Heat detector (oUL 521) with five (5) possible field -selectable temperatures; combined with four (4) rate -of -rise options • Direct, in -duct (plenum) detector (oUL 268A) • Supervisory monitoring for temperature ranges • NFPA 76 (Telco Standard) as VEWFD • Low -temperature warning signal at 40°F (4.4°C) — for sprinkler systems, per NFPA 25 I NFPA 72 Model 0OH941 —which provides extremely accurate and reliable fire detection with built-in redundancy— utilizes advanced, multi -criteria detection technology known as ASA (Advanced Signal Analysis) that allows the detector to distinguish non -threatening deceptive phenomena. For instance, the signals from the detector's sensors are monitored and processed via the ASA-patented algorithm technology, which combines the signals into a neural network to create an intelligent, multi -criteria detector. The encompassing result is a detector that provides enhanced detection to a wide range of products of combustion —while offering unsurpassed rejection to nuisance -alarm sources, such as: dust, steam, aerosols and other deceptive phenomena that could cause false alarms. Since Model 0OH941 is a (2) two -wire, addressable device, it is able to function as a multi -purpose detector — satisfying smoke and heat detection in a singular, aesthetically pleasing package. Further, Model 0OH941 serves as an extremely cost-effective, viable solution that saves product, installation and maintenance costs (compared to other multiple -detector alternatives). Each detector fits into one (1) wall -or -ceiling footprint, and only occupies one (1) address on the signal -line circuit (SLQ. A patented forward -and -backward, light -scattering technology —which is able to distinguish both small and large products of combustion — operates at the core of each Model 0OH941 detector. Additionally, each Model 0OH941 provides an environmental -friendly solution to ionization detectors, eliminating the need for a radioactive source and eventual disposal requirements. Thus, each detector is capable of detecting both smoldering and flaming fire —all in ecologically efficient manner —and is a valid, RoHS- compliant (Restriction of Hazardous Substances) detection alternative to ionization detectors. Two (2) thermal sensors make each Model 0OH941 detector a robust, reliable device suitable for the most challenging applications. SIEMENS Industry, Inc. Building Technologies Division Operation Forward -and -Backward Light -Scattering Technology 1. Heat sensors 2. Receiver 3. Backward scatterer 4. Forward scatterer 5. Labyrinth The high -quality, optical -electronic measuring chamber for each Model 0OH941 houses the following components: ✓ Two (2) optical transmitters ✓ One (1) optical receiver ✓ Two (2) thermal sensors The transmitters illuminate the smoke particles from different angles: one sensor acts as forward scatterer, the other sensor as a backward scatterer. The scattered light then hits the receiver (photodiode) and generates a measurable electric signal. The combination of a forward -and -backward scatterer facilitates optimum detection, as well as differentiates between light -and -dark particles 1 particle size. This type of detection creates standardized, responsive behavior, thus optimizing the differentiation between wanted signals and deceptive phenomena. In addition, the heat sensors make it possible to detect fires without smoke generation. This scenario generates the following advantages: ✓ Early detection of all fire types of fire —whether they generate light -or -dark smoke, or no smoke ✓ The fire detector can be operated at a lower sensitivity level, thus achieving a higher immunity against false alarms that may otherwise be caused by cold aerosols (e.g. — by smoking, electrical welding, etc.). In the case of an open fire, the smoke sensitivity is heightened by a temperature increase —which means that a detection -reliability level that is comparable to a wide -spectrum smoke detector — can be achieved and maintained. Note: For Model 0OH941 compatibility to FireFinder® XLS, the XLS FACP requires Model PMI-2 (no firmware upgrade required), or Model PMI (firmware Rev. 9 or higher is required). The detector's compatibility also requires both of following: - Rev. 9 (or higher) ZEUS custom -configuration software - Rev. 6 (or higher) Device Loop Card (DLC) firmware CerberusTM PRO Operation — (continued) Field -Device Programmer / Test Unit Model 0OH941 is compatible with the Device Program 1 Test Unit accessory, which is used to program and verify the address of the detector. The technician selects the accessory's program mode, and enters the desired address. Model 87201 DPU automatically sets and verifies the address and tests the detector. Model 8720 / DPU eliminates the need for cumbersome, unreliable mechanical programming methods— such as dials or switches — and reduces installation and service costs by electronically programming and testing the detector prior to installation. Model 8720 / DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programmer and testing equipment from practically any location. When in'test' mode, Model 8720 / DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly. Field -selectable application profiles Model 0OH941 provides 22 user-friendly, field -selectable application profiles, indentified with universally known names (e.g. — Hotel, Telco, Office, Parking Garage, Dormitory, and Data Centeretc.) Referto installation manual: P/N— A6v10324655 for a complete list and description of application profiles. Due to generic -name classification, no cross-reference tables are required as the application name resides in the panel's configuration tool. This user-friendly feature— along with the algorithms provided byASAtechnology— provides a reliable, field -configurable detector suitable for an array of applications. Field -selectable temperature settings Model 0OH941 provides five (5) field -selectable temperature thresholds, ranging from 1350F to 175T (57°C to 79°C), with fixed and rate -of -rise options. These ranges provide maximum flexibility to program and to easily adjust the temperature settings that suit multi -application needs within a building or changing environmental conditions. Additionally, Model 0OH941 can be configured to provide a low -temperature warning signal at 40T (4.4°C). This configuration (along with connection to a compatible fire alarm control panel {FACP}) meets NFPA 72 requirements for sprinkler -temperature monitoring, and serves as prevention of water freezing in pipes for water -based suppression systems. SIEMENS Industry, Inc. Building Technologies Division Ambient supervisory feature for temperature -threshold ranges Another highlight for Model 0OH941 is supervision of ambient temperatures, allowing the end user to set an unique, specified warning point at a customized temperature threshold ranging from -47 to 120°F (-20°C to 49 °C). This feature is practical for monitoring of machinery; special processes, or for environments where maintaining a temperature is critical as an early -warning supervisory signal. Self -monitoring for smoke -sensor sensitivity Model 0OH941 provides an automatic self -monitoring sensitivity check that complies with the NFPA 72 sensitivity requirements. When connected with a compatible FACP, it provides automatic and dynamic sensitivity verification within the agency -listed -and -approved limits. Besides checking for sensor integrity and automatic environmental compensation, Model 0OH941 provides a display and report of sensitivity in percent -per -foot (or percent -per -meter) at the FACP. Profile Overview The Model 0OH941 detector contains a tri-color LED indicator, capable of flashing anyone (1) of three (3) distinct colors: green, or red. During each flash interval, the microprocessor -based detector monitors the following: • Smoke in its sensing chamber • Smoke sensitivity is within the range indicated on the nameplate label • Internal sensors and electronics Based on the results of the monitoring, the LED indicator flashes the following: Flash Flash Condition Interval Color (in seconds) Normal supervisory operation. Green*: Smoke sensitivity is within rated 10 limits. Yellow: Detector is in trouble and needs 4 replacement. Red: Alarm condition. 1 No Flash: Detector is not powered. -- * LED can be turned OFF. Please follow the corresponding description of the panel used. A quick, visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from each Cerberus PRO FACP, indicating the status and settings assigned to each individual detector. CerberusTM PRO Installation All Model 0OH941 detectors use a surface -mounting base (Model DB-11 or Model DB-11 E), which mounts on a 4-inch octagonal, square or single -gang electrical box. The base utilizes screw -clamp contacts for electrical connections and self -wiping contacts for increased reliability. The Model DB-11 base can be used with the optional Model LK 11 detector locking kit, which contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has decorative plugs to cover the outer mounting screw holes. Model 0OH941 may be installed on the same initiating circuit with the Siemens Model'H'-series detectors [when used with Cerberus PRO FACPs] — • Models HFP-11, HFPT-11 • Model'HMS'-series manual stations • Model'HTRI'-series interfaces • Model HCP output -control devices • Model 'HZM'-series of addressable, conventional zone modules Each detector consists of the following: • Dust -resistant photoelectric chamber • Solid state, non -mechanical thermal sensor • Microprocessor -based electronics with a low -profile plastic housing Each Model 0OH941 fire detector is shipped with a protective dust cover: 2 1) Ma31 00X941 detector / � • 1 2) Dust 07OeT / (provided ^..pith eat detector) All Model 0OH941 detectors are approved for operation within the OUL-specified temperature range of 32' to 120°F (0' to 49°C) — depending on heat -detector configuration (see to installation manual: PIN A6V1 0324655) for details. Application Data Installation of Model 0OH941 detectors requires a two - wire circuit. In many retrofit cases, existing wiring may be used. 'T-tapping' is permitted only for Style 4 (Class B) wiring. Model 0OH941 is polarity insensitive, which can greatly reduce installation and debugging time. SIEMENS Industry, Inc. Building Technologies Division Model 0OH941 fire detectors can be applied within the maximum 30-feet center spacing (900 sq. ft. areas,) as referenced in NFPA 72. This application guideline is based on ideal conditions —specifically, smooth ceiling surfaces; minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire -protection - system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens — Fire Safety distributor or sales office whenever you need assistance applying Model 0OH941 in unusual applications. Be sure to follow NFPA guidelines and OUL Listed / ULC Listed installation instructions — included with every Siemens — Fire Safety detector —and local codes as for all fire protection equipment. Technical Data Operating Temperatures: +32°F (0°C) to 120°F (49°C) depending upon heat -detector configurations (see to installation manual: P/N A6V10324655) for details Heat -Detector Range: +135°F (57°C) to 17YF (79°C) Thermal Rating: 00H941 Selectable Temp. Profiles Fixed temperature 135)F Fixed temperature 1451F Fixed temperature 1550F Fixed temperature 1650F Fixed temperature 1750F Fixed temperature 135°F + Rate of Rise (RoR) 15OF Fixed temperature 1751F + Rate of Rise (RoR) 151F Fixed temperature 1350F + Rate of Rise (RoR) 201F Fixed temperature 1751F + Rate of Rise (RoR) 201F Selectable Alarm Threshold Setting Profiles 2.50 % / ft.Threshold 3.00 % / ft.Threshold 2.50 % ! ft.Threshold, verified 3.00 %,' ft.Threshold, verified CerberusTM PRO Technical Data — (continued) Detector Sensitivity Range: OUL: 0.77% to 3.82% I ft. NFPA 76 (Telco) VEWFD: 0.2% 1 ft. Pre -alarm, 1.0% I ft. Alarm Application Profiles: 22 (field configurable) Programmable Supervisory Temperature Warning available with compatible FACPs: -4°F (-20°C) to 120°F (49°C) Relative Humidity: 0-95%; non -condensing Air Velocity — (Open Area): 0 - 4,000 feet -per -minute (fpm) Direct -in -Duct: 0 - 4,000 (fpm) Air Pressure: No effect Maximum Spacing: 30-foot centers (900 sq. ft.), per NFPA 72 and ULC-S524 Listed Input Voltage Range: 13VDC - 32VDC Alarm Current: 650pA, max. Quiescent (Standby) Current: 280pA - 360pA Detector Weight: 0.281 lbs. (0.128 kg.) Approvals / Standards: FM 3210, 3220 CSFM 7272-0067:0260 oUL 268 NFPA 25 ©UL 268A NFPA 72 (DUL 521 NFPA 76 ULC-S524 Listed SIEMENS Industry, Inc. Building Technologies Division Mounting Diagrams Dimensions 4.1- (10.4 cm.) e� ,.s.. Model 0OH941 6.1" (15.5 cm.) , .s.. Model 0OH941 with Model DB-11 base (11.7cm.) 0 T Model 0OH941 with Model DB-11 E base Detector Compatibility Table Data Model Number Sheet Description Number — 6300 FireFinder0 XLS (system overview) DLC 6312 Device Loop Card 50-point panel MIT] 252-point system (networkable) 504-point system (networkable) CerberusTM PRO Details for Ordering Model Number Part Number Description 0OH941 S54320-F7-A2 Multi -Criteria Fire Detector with ASAtechnolo TM DB-1 1 E 500-094151 E Detector Base {small} D132-HR S54320-F12-A1 Detector Mounting Base with Relay RL-HC 500-033230 Remote Alarm Indicator: 4" octagon -box mount, red RL-HW 500-033310 Remote Alarm Indicator: single -gang box mount, red LK-11 500-695350 Base Locking Kit In Canada, order: Model Part I Number Description Number DB-11 C 500-095687 1 Detector Mounting Base for ULC (Listed) SIEMENS CerberuSTM PRO Siemens Industry, Inc. — Building Technologies Div 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO Building Technologies Division SII —Fire Safety [Printed in U.S.A ] NOTICE —The information contained in this data -sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information. Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer. Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer. March 2013 — Supersedes sheet dated 2/2013 ( Rev. 2 ) S niso L-Series and L-Series with LED Indoor Selectable Horns, Strobes and Horn Strobes System Sensor L-Series and L-Series with LED audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features • LED technology provides lower current draw • Digital Voltage Meter (DVM) diagnostic test points for Horn Strobes and Strobes • Common aesthetics across the L-Series platform • Standard and compact sizes • Tamper -resistant construction • Field -selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 • Field -selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 • Rotary switches for candela, tone and volume selections • Mounting plate provides plug-in design for easier installation and shorting springs to check wiring continuity • Electrically compatible with legacy SpectrAlert, SpectrAlert Advance and L-series devices • Synchronization through use of UL approved power supplies that support System Sensor Sync protocol or System Sensor MDL3 Sync Module • Horns, Strobes and Horn Strobes listed for wall or ceiling use Agency Listings SIGNALING SIGNALING C UL US U� ULC FM 0LISTED LISTED LISTED APPROVED Horn Strobes Horns: Horns: 3057072 7300-1653:0525 and Strobes: 54011 S4011 FM23FPUS0195 7135-1653:0503 55512, 54011 7135-1653:0526 f I E E The System Sensor L-Series and L-Series with LED platform offers the most versatile and easy -to -use line of horns, strobes, and horn strobes in the industry with lower current draw and modern aesthetics. LED lighting technology offers significantly lower current draw compared to older Xenon bulbs across a full candela range. This improves design flexibility for notification appliance circuits (NACs) while also reducing power supply requirements allowing for simpler and lower cost installations. Flexible design options meet virtually any application requirement: wall or ceiling mount, standard or compact sizes, red or white color choices, bezel kits for alternate markings and languages, and LED color lenses for distinctive visual signaling. In addition, installers can easily adapt devices using field selectable candela, tone and volume settings using rotary switches. The L-Series and L-Series with LED line is developed to simplify installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. The universal mounting plate includes an onboard shorting spring, so installers can test wiring continuity before the device is installed. In addition, the System Sensor L-Series with LED notification appliances offer a new diagnostic test point feature that allows you to measure device voltage with a digital voltage meter (DVM) without removing the appliance from the wall or ceiling. The DVM test points are discreetly located on the face of the notification appliance which enable faster troubleshooting and end of line (EOL) voltage checks while greatly reducing the risk of misplacing or damaging appliances during troubleshooting. AVDS916-01 • 10/03/2023 • Page 1 L-Series and L-Series with LED Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non -condensing Strobe Flash Rate 1 flash per second Nominal Voltage, LED Strobes and Horn Strobes Regulated 24 VDC Nominal Voltage, Horns Regulated 12 VDC or regulated 24 DC/FWR Operating Voltage Range, LED Strobes and Horn Strobes 16 to 33 V (24 V nominal) Operating Voltage Range, Horns 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG UUULC Current Draw Data, Horn Tones, and Sound Output Data Candela Rating 16-33 Volts Wall Ceiling Candela 15 18 18 Range 30 22 22 75 70 70 95 75 75 110 85 — 115 — 90 135 105 — 150 — 110 177 — 115 185 120 — Sound Pattern dB 8-17.5 Volts DC 16-33 Volts DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non -Temporal High 43 47 54 Non -Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non -Temporal High 42 43 54 3.1 KHz Non -Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 Maximum Horn StrobeUIJULC • .: Current Draw (mA RMS), Horn Strobe, Candela Range (15-185 cd) Sound Output (dBA) Switch Pos. Sound Pattern Volume Setting 15cd 30cd 75cd 95cd 16-33 Volts 110cd 115cd WALL CEILING 135cd WALL 150cd CEILING 177cd CEILING 185cd WALL 16-33V DC 1 Temporal High 35 38 87 92 94 120 189 189 190 190 87 2 Temporal Low 35 38 87 92 94 120 135 135 145 145 79 3 Non -Temporal High 50 52 87 92 94 120 127 127 135 135 87 4 Non -Temporal Low 35 38 87 92 94 120 125 125 130 130 79 5 3.1 KHz Temporal 3 High 35 38 87 89 91 115 155 155 165 165 86 6 3.1 KHz Temporal 3 Low 35 38 87 89 91 115 128 130 135 135 80 7 3.1 KHz Non -Temporal High 40 42 87 89 91 115 125 125 135 135 86 8 3.1 KHz Non -Temporal Low 35 38 87 89 91 115 120 120 130 130 80 AVDS916-01 • 10/03/2023 • Page 2 L-Series with LED Dimensions: Wall -Mounted Equipment 2.07" (63 mm) —� 3.46" _ 3.46" 125' 88 mm 1.25' 3.57" 1.55' . 88 mm 32 mm (9.1 cm) (3.9 cm) (31.8 mm) p0opopopopopopo opop9p.popopoop opo ppppppopopopo 5Frt 5.27' o 0 o OpOp4popopop0 O 133.9 mm e 3.27" pppppopppppp (13.7 cm) 133.9 mm 4p4p4p4ppppp" pppppp°p°p°p0 A0617-00 A0547-00 A0557-00 Compact Strobe, Horn Strobe Compact Horn Compact Surface Mount Back Box for Wall for Walls (SBBGRL, SBBGWL) 'II,�III�I' A0613-00 Strobes, Horn Strobes for Walls L-Series with LED Dimensions: Ceili 6.83" diam. (173.5 mm) Strobes and Horn Strobes for Ceilings Horn ounted A0608-00 1.25" 4.82" 32 mm (12.24 cm) 69 (4.69 cm) LIP 5.78" O (14.68 cm) �® ® 0 A0549-00 A0554-01 Surface Mount Back Box for Walls (SBBRL/SBBWL) uiament 6.92" diem (175. 2.5' (64 mm) O A0546-00 Surface Mount Back Box for Ceilings (SBBGRL, SBCWL) AVDS916-01 • 10/03/2023 • Page 3 L-Series with LED: Ordering Information ModelDescription ModelDescription L-Series with LED Horn Strobes LED Lenses P2RLED 2-Wire, Horn Strobe, Wall, Red LENS-A3 Lens LED Amber Wall/Ceiling P2RLED-B 2-Wire, Horn Strobe, Wall, Red, Bilingual LENS-133 Lens LED Blue Wall/Ceiling P2WLED 2-Wire, Horn Strobe, Wall, White LENS-133 Lens LED Green Wall/Ceiling P2WLED-B 2-Wire, Horn Strobe, Wall, White, Bilingual LENS-R3 Lens LED Red Wall/Ceiling P2GRLED 2-Wire, Compact Horn Strobe, Wall, Red Accessories P2GRLED-B 2-Wire, Compact Horn Strobe, Wall, Red, Bilingual TR-2 Universal Wall Trim Ring Red P2GWLED 2-Wire, Compact Horn Strobe, Wall, White TR-2W Universal Wall Trim Ring White P2GWLED-B 2-Wire, Compact Horn Strobe, Wall, White, SBBWL Wall Surface Mount Back Box, Red Bilingual SBBWL Wall Surface Mount Back Box, White P2RLED-P 2-Wire, Horn Strobe, Wall, Red, Plain SBBGWL Compact Wall Surface Mount Back Box, Red P2WLED-P 2-Wire, Horn Strobe, Wall, White, Plain SBBGWL Compact Wall Surface Mount Back Box, White P2RLED-SP 2-Wire, Horn Strobe, Wall, Red, FUEGO TRC-2 Universal Ceiling Trim Ring, Red P2WLED-SP 2-Wire, Horn Strobe, _Wall, FUEGO TRC-2W Universal Ceiling Trim Ring, White SBBCWL Ceiling Surface Mount Back Box, Red PC2RLED-B 2-Wire, Horn Strobe, Ceiling, Red, Bilingual SBBCWL Ceiling Surface Mount Back Box, White PC2WLED 2-Wire, Horn Strobe, Ceiling, White Bezelst PC2WLED-B 2-Wire, Horn Strobe, Ceiling, White, Bilingual BZR Wall Red Bezel Kit L-Series with LED Strobes BZW Wall White Bezel Kit SRLED Strobe, Wall, Red BZGR Compact Wall Red Bezel Kit SRLED-B Strobe, Wall, Red, Bilingual BZGW Compact Wall White Bezel Kit SWLED Strobe, Wall, White BZRC Horn Strobe Ceiling Red Bezel Kit SWLED-B Strobe, Wall, White, Bilingual BZWC Horn Strobe Ceiling White Bezel Kit SGRLED Strobe, Compact, Wall, Red SGRLED-B Strobe, Compact, Wall, Red, Bilingual Notes for L-Series With LED Horn Strobes and Strobes: SGWLED Strobe, Compact, Wall, White All -P models have a plain housing (no "FIRE" marking on cover). All -SP models have "FUEGO" marking on cover. SGWLED-B Strobe, Compact, Wall, White, Bilingual All -ALERT models have "ALERT' marking on cover. SRLED-P Strobe, Wall, Red, Plain All -B models have "FIRE/FEU" marking on cover for use in Canadian SWLED-P Strobe, Wall, White, Plain applications. SRLED-SP Strobe, Wall, Red, FUEGO Amber lenses are not for use in Canadian applications SWLED-CLR- Strobe, Wall, White, ALERT Notes for L-Series Horns: ALERT "Horn -only models are listed for wall or ceiling use. SWLED-ALERT Strobe, Wall, White, ALERT, Amber Lens SCRLED Strobe, Ceiling, Red Notes for Bezels: SCRLED-B Strobe, Ceiling, Red, Bilingual tEach bezel pack ships in a package of 5. SCRLED-P Strobe, Ceiling, White, Plain Add one of the following extensions for print/language options: -F (FIRE), -AL (ALERT), -EV (EVAC), -AG (AGENT), -P (Plain), -FR (FEU), -PG (FOGO), -SP SCWLED Strobe, Ceiling, White (FUEGO), -SPE (FUEGO/FIRE). SCWLED-B Strobe, Ceiling, White, Bilingual SCWLED-P Strobe, Ceiling, White, Plain SCWLED-CLR- Strobe, Ceiling, White, ALERT ALERT L-Series Horns HRL* Horn, Red HRLA` Horn, Red, Plain, ULC HWL" Horn, White HWLA' Horn, White, Plain, ULC HGRL' Compact Horn, Red HGRLA" Compact Horn, Red, Plain, ULC HGWL" Compact Horn, White HGWLA' Compact Horn, White, Plain, ULC 3825 Ohio Avenue • St. Charles, IL 60174 USA System Sensor® is a registered trademark Phone: 800-SENSOR2 •Fax: 630-377-6495 of Honeywell International, Inc. www.systemsensor.com SYSTEM 3333 Unity Drive, Mississauga, ON L5L 3S6 Canada ©2023System Sensor. Phone: 800 SENSOR2 •Fax: 905 812-0771 Product specifications subject to change without notice. visit systemsensorcom or current product information, including the latest version of this data sheet. SENSOR' www.systemsensor.ca AVDS916-01.10/03/2023