170109 MAD (WSEC-LGT).pdfLighting Summary LGT-SUM
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Info Project Title:Date 1/
For Building Department Use
Company Name:
Company Address:
Applicant Name:
Applicant Phone:
Applicant Email:
Project Description FALSE
Building Additions Interior lighting Exterior lighting
Interior and Exterior Interior lighting Parking garage Exterior lighting
Lighting Alterations
Interior lighting Parking garage Exterior lighting
Change of Space Use
Lighting Controls
MADRONA SCHOOL REPLACEMENT
TRAVIS FITZMAURICE & ASSOCIATES
1200 WESTLAKE AVE N
APRILLE BALANGUE
Compliance Method
203.285.7228
APRILLE@TRAVISFITZMAURICE.COM
Lighting Power
New Building Addition Alteration Plans Included
Compliance forms do not require a password to use. Instructional and calculating cells are write-protected.
Applicant Information. Provide contact information for individual who can respond to inquiries about compliance form information provided.
Include PROJ-SUM form (included in envelope forms workbook) with lighting complliance forms.
Existing interior lighting systems in areas under-going a change in space use are upgraded to
comply with LPAs for the new space types per Tables C405.4.2(1) or C405.4.2(2).
Lamp and/or ballast replacement only –
existing total wattage not increased
New wiring installed to serve added
fixtures and/or fixtures relocated to new
circuit(s)
New or moved lighting panel
Interior space is reconfigured -
luminaires unchanged or relocated only
No changes are being made to
the interior or exterior lighting
systems and existing space
uses and configuration are not
changed.
50% or more of existing are replaced
50% or more replaced -Total lighting power of new + existing-to-remain fixtures shall comply with total
LPA per Sections C405.4.2 and C405.5.2. Include new + existing-to-remain fixtures in Proposed Lighting
Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
Less than 50% replaced -Total lighting power of new + existing-to-remain fixtures shall not exceed the
total lighting power prior to alteration. Include new + existing-to-remain fixtures in the Proposed Lighting
Wattage table in LTG-INT-BLD, LTG-INT-SPACE or LTG-EXT form.
50% threshold applies to number of luminaires for interior spaces and parking garages, and total
installed wattage for exterior luminaires.
Less than 50% of existing are replaced
New wiring or circuit -For interior lighting, provide required manual controls per C405.2.3, occupancy
sensor controls per C405.2.1, daylight responsive controls per C405.2.4 and application specific lighting
controls per C405.2.5. For exterior lighting, provide required controls per C405.2.7.
New or moved panel -Provide all applicable lighting controls as noted for New Wiring and automatic
time switch controls per C405.2.2.
Reconfigured interior space -Provide all required lighting controls that apply to a new interior space.
Application specific lighting control provisions per C405.2.5 do not apply to reconfigured spaces.
Select all Lighting Power and Lighting
Control elements that apply to the scope
of the retrofit project. If project includes a
combination of spaces where less than
50% of the existing fixtures are replaced in
some spaces, and 50% or more of the
fixtures are replaced in others, then
provide separate lighting power
compliance forms for the two retrofit
conditions. Spaces undergoing the same
type of retrofit may be combined into one
lighting power compliance form.
Refer to Section C503.6 for additional
requirements.
All alteration lighting controls shall be
commissioned per C408.3.
Identify interior spaces requiring LPD upgrade to the current Code in Proposed Lighting Wattage table in
LTG-INT-BLD or LTG-INT-SPACE form.
Addition is combined with existing:
For interior lighting projects, include new + existing interior lighting fixture wattage in Proposed Lighting
Wattage table in LTG-INT-BLD or LTG-INT-SPACE form.
For exterior lighting projects, include new + existing exterior lighting fixture wattage in Proposed
Tradable and Proposed Non-Tradable Lighting Wattage tables in LTG-EXT form.
Refer to Section C502.2.6 for additional
requirements.
Lighting systems in addition area comply with all applicable
provisions as a stand alone new construction project
Lighting systems in addition are combined with existing
building lighting systems to demonstrate compliance
1/9/2016
Lighting Summary, cont.LGT-SUM
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Title:MADRONA SCHOOL REPLACEMENT Date 1/
Interior Lighting System
Description
Interior Lighting Controls FALSE
Interior Lighting Power
Allowance Method
Dwelling Unit Interior
Lighting
Exterior Lighting System
Description
Exterior lighting systems will be LED type. Outdoor circulation areas and parking lots will be
illuminated by LED light sources. Lighting systems shall be designed to provide illumination
levels in accordance with the recommendations of the Illuminating Engineering Society (IES),
consistent with Energy Code.
Select method used in project.
C406.3 High Efficacy Lighting
C405.2 thru C405.5 Commercial Lighting Controls and LPA
Permanently installed interior lighting fixtures in dwelling units comply with:
To comply with C406.4, no less than 90% of the total installed interior lighting power shall comply with the
required controls per C406.4.
All C405.2.1 -C405.2.8 Controls
Additional Efficiency Package Option
C406.4 Enhanced digital lighting controls
C405.2 Exception 5 Luminaire Level
Lighting Control (LLLC)
Building Area Method Space-by-space Method
Interior lighting fixtures will be LED. Lighting will be energy efficient and shall be pendant,
surface mounted, or recessed. Tunable lighting will be considered as an alternate. Lighting
systems shall be designed to provide illumination levels in accordance with the
recommendations of the Illuminating Engineering Society (IES), consistent with Energy Code.
1/9/2016
Interior Lighting - Building Area Method LTG-INT-BLD
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Title:MADRONA SCHOOL REPLACEMENT Date 1/
For Building Department Use
LPA
Calculation
Type
Maximum Allowed Lighting Wattage
Building Area
Location (plan #,
room #, or ALL)Area Description
Gross Interior
Area in ft2
Allowed
Watts per ft2
Watts Allowed
(watts/ft2 x area)
School/university ALL School 80000 0.70 56000
Total 80000
Proposed Lighting Wattage
Building Area
Location (plan #,
room #)Fixture Description NOTE 2, 3, 4, 5 Number of
Fixtures
Watts per
Fixture NOTE 6 Watts Proposed
School/university ELEC/MECH RM PL-1: LED 48 W 42 114 4788
School/university GYM PL-2: LED 188 W 25 188 4700
School/university STORAGE PL-3: LED 30 W 6 30 180
School/university BAND, CHOIR PL-4: LED 55 W 36 55 1980
School/university CLASSROOM PL-5: LED 55 W 32 55 1760
School/university GYM PL-6: LED 47 W 7 47 329
School/university MECH STORAGE PL-7: LED 24 W 5 24 120
School/university CLASSROOM RL-1: LED 50 W 251 50 12550
School/university
OFFICE,
CORRIDOR,
CLASSROOM
RL-2: LED 32 W 320 32 10240
School/university STORAGE RL-3: LED 35 W 12 35 420
School/university KITCHEN RL-4: LED 76 W 11 76 836
School/university COMMONS RL-5: LED 37 W 59 37 2183
School/university STAGE RL-6: LED 20 W 7 20 140
School/university STORAGE,
RESTROOM SL-1: LED 30 W 37 30 1110
School/university NURSE WL-2: LED 19 W 2 19 38
Compliance by Building Area NOTE 7
Building Area
Total Allowed
Watts
Total Proposed
Watts
Interior Lighting
Power Allowance
School/university 56000 41374 COMPLIES
Totals 56000 41374
Calculation
Area NOTE 8
Warnings
Note 1 -List all unique building areas per Table C405.4.2(1) that occur in the
project scope. Select building area category from drop down menu.
Note 2 -Proposed fixtures must be listed in the building area in which they occur. List all proposed lighting fixtures including exempt
lighting equipment and existing-to-remain fixtures.
Note 3 -For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), number of lamps in the fixture, and ballast type (if included).
For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
Note 4 -For lighting equipment eligible for exemption per C405.4.1, note exception number and leave Watts/Fixture blank.
Note 5 -Existing-to-remain fixtures shall be included in the Proposed Lighting Wattage table in the same manner as new fixtures. Identify as
Addition
+ existing
Addition -
stand alone
Spaces where ≥ 50% of
luminaires are replaced
Spaces where < 50% of
luminaires are replaced
To comply with C406.3, the Proposed LPD shall be 25% lower than the Target LPA.
Refer to C406.3 for additional requirements.
Additional Efficiency Package Option
C406.3 Reduced Interior Lighting PowerStandard
NOTE 1
1/9/2016
g p g g g y
existing in fixture description.
Note 6 -For proposed Watts/Fixture enter the luminaire wattage for installed lamp and ballast using manufacturer or other approved source. For
luminaires with screw-in lamps, enter the manufacturer's listed maximum input wattage of the fixture (not the lamp wattage). For low voltage
lighting, enter the wattage of the transformer. For line voltage track/busway systems, enter the larger of the attached luminaire wattage or
50 watts/lineal foot, or enter the wattage limit of permanent current limiting device.
Note 7 -Proposed Wattage for each Building Area type shall not exceed the Allowed Wattage for that Building Area type. Trading wattage
between Building Area types is not allowed under the Building Area Method compliance path.
Note 8 -Calculation Area Details:
a. Lighting fixtures in a building addition may comply as a stand alone project, or they may be combined with the overall existing building
lighting systems to demonstrate compliance. Refer to C502.1.
b. For alterations and building additions, provide Building Area types and gross interior areas in the Maximum Allowed Lighting Wattage
table. If a building addition will comply as combined with the overall existing builidng lighting systems, include all applicable existing
Building Area types and gross interior areas.
c. If less than 50% of existing lighting fixtures will be replaced, use LTG-INT-SPACE form to document compliance.
Exterior Lighting LTG-EXT
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Title:MADRONA SCHOOL REPLACEMENT Date 1/
For Building Department Use
Building Grounds
Tradable Maximum Allowed Lighting Wattage NOTE 1 Base Site Allowance:600
Tradable Surfaces Surface Description
Area (ft2), perimeter (lf)
or # of items
Allowed Watts
per ft2 or per lf
Allowed Watts
x ft2 (or x lf)
Uncovered Parking and drives UNCOVERED PARKING AND DRIVES 128733 0.06 W/ft2 7724
Grounds Walkways >10' wide GROUNDS WALKWAYS > 10' WIDE 35213 0.14 W/ft2 4930
Stairways STAIRS 639 1.0 W/ft2 639
Entry Canopies ENTRY CANOPIES 12283 0.25 W/ft2 3071
Total Allowed Tradable + Site Allowance Watts:16964
Tradable Proposed Lighting Wattage NOTE 2
Tradable Surface Fixture Description NOTE 3, 4 Number of
Fixtures
Watts per
Fixture NOTE 5 Watts
Proposed
Uncovered Parking and drives P2: LED 540 W 4 540 2160
Uncovered Parking and drives P3: LED 270W 12 270 3240
Grounds Walkways >10' wide PD: LED 134 W 8 134 1072
Grounds Walkways >10' wide RL-7: LED 19 W 36 19 684
Grounds Walkways >10' wide WL-3: LED 40 W 17 40 680
Stairways PD: LED 134 W 3 134 402
Entry Canopies RL-7: LED 19 W 107 19 2033
Total Proposed Tradable Watts:10271
Non-Tradable Maximum Allowed Lighting Wattage NOTE 1 Site Allowance Remaining: 600
Non-Tradable Surfaces Surface Description
Area (ft2), perimeter (lf)
or # of items
Allowed Watts
per ft2 or per lf
Allowed Watts
x ft2 (or x lf)
Non-Tradable Proposed Lighting Wattage NOTE 2
Non-Tradable Surface Fixture Description NOTE 3, 4 Number of
Fixtures
Watts per
Fixture NOTE 5 Watts
Proposed
Non-Tradable Watts Exceeding LPA:0
Remaining Site Allowance:600
Exterior Lighting COMPLIES WITH MAX. ALLOWANCE
Calculation Area
Exterior Lighting
Zone Zone 4
Exemption
Controlled by motion sensor
Zone 3Zone 2Zone 1
Non-tradable proposed watts may not exceed allowed watts for any individual
surface unless the total excess watts for all non-tradable surfaces are less than the
remaining site allowance.
Total proposed tradable watts may not exceed the sum of total allowed tradable
watts plus the base site allowance. Any base site allowance not needed to make
tradable watts comply can be applied to individual non-tradable categories.
Table C405.5.2(1)
Specified by jurisdiction.
Addition
+ existing
Addition -
stand alone
Alteration with ≥ 50% ext.
wattage replaced
Alteration with < 50%
ext. wattage replaced
Zone selection required to enable LTG-EXT form
Applies to luminaires >
100 Watts
Efficacy > 80 lumens/watt
Note 1 -List all unique exterior sufaces per Table C405.5.2(2) that occur in the project scope. Select exterior surface categories from drop
down menu.
N t 2 Li t ll d li hti fi t i l di i ti t i fi t
1/9/2016
Note 2 -List all proposed lighting fixtures including existing-to-remain fixtures.
Note 3 -For proposed Fixture Description, indicate fixture type, lamp type, number of lamps in the fixture, and ballast type (if applicable).
Note 4 -Existing-to-remain fixtures shall be included in the Tradable and Non-Tradable Proposed Lighting Wattage tables in the same manner
as new fixtures. Identify as existing in fixture description.
Note 5 -For proposed Watts/Fixture enter the luminaire wattage for installed lamp and ballast using manufacturer or other approved source. For
luminaires with screw-in lamps, enter the manufacturer's listed maximum input wattage of the fixture (not the lamp wattage). For low
voltage lighting, enter the wattage of the transformer.
Lighting, Motor, and Electrical Permit Checklist, Pg. 1 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Title: MADRONA SCHOOL REPLACEMENT Date 1/
Applicability
(yes,no,na)Code Section Component Compliance information required in permit documents
Location in
Documents
Building Department
Notes
LIGHTING CONTROLS
Yes C405.2 Lighting controls,
general
For all lighting fixtures, indicate lighting control method on plans
for spaces and lighting zone(s) served, or exception taken E-2XX SHEETS
No C405.2
Luminaire level
lighting controls
(LLLC)
Indicate on plans all fixtures provided with LLLC in lieu of
C405.2 lighting controls; provide description of control
capabilities and performance parameters
NA C405.1 Lighting in dwelling
units
For permanently installed lighting fixtures in dwelling units,
indicate lighting control method on plans for spaces and
lighting zone(s) served, or demonstrate compliance with high
efficacy exception
Yes
C405.2.3
C405.2.1.1
C405.2.2.2
C405.2.4
C405.2.5
Manual controls
Indicate on plans the method of manual lighting control (whether
combined with occupancy sensor, automatic light reduction,
daylight responsive or specific application controls), location of
manual control device and area or specifice application it
serves
E-2XX SHEETS
Yes C405.2.2.1
C405.2.2.2
C405.2.3
Manual interior
lighting controls
Indicate on plans which method of manual 50% lighting load
reduction is provided, or whether lighting load is reduced via
occupancy sensors or daylight responsive controls
E-2XX SHEETS
Indicate on plans the method of automatic shut-off control
during unoccupied periods (occupancy sensor or time switch)
for all lighting zones;
E-2XX SHEETS
Indicate locations where automatic shutoff is provided by other
methods (occupancy sensor or digital timer switch) or which
time switch control exception applies
E-2XX SHEETS
Indicate on plans the spaces served by occupancy sensors;E-2XX SHEETS
Indicate whether occupancy sensor controls are configured to
be manual-on, automatic 50%-on, or serve a space eligible for
automatic 100%-on per exception
E-2XX SHEETS
NA C405.2.1.2
Occupancy sensor
controls -
warehouses
Indicate aisleways and open areas in warehouse spaces
provided with occupancy sensor controls that reduce lighting
power by 50%
NA C405.2.6 Digital timer switch Indicate required digital timer switch control function when
control is used
C405.2.2.1 Automatic time
switch controls
Indicate locations of override switches on plans and the lighting
zone(s) served, include area sq. ft.
Indicate primary and secondary sidelight daylight zone areas on
plans, include sq. ft.;E-2XX SHEETS
Indicate toplight daylight zone areas on plans, include sq. ft.;E-2XX SHEETS
For small vertical fenestration assemblies (rough opening less
than 10 percent of primary daylight zone) where daylight
responsive controls are not required, provide fenestration area
to daylight zone calculation(s)
Indicate on plans lighting zone(s) served by daylight responsive
controls;E-2XX SHEETS
Identify sidelight and toplight daylight zones that are not
provided with daylight sensing controls and the exception(s) that E-2XX SHEETS
Indicate on plans the lighting load reduction method -
continuous dimming, or stepped dimming that provides at least
two even steps between 0%-100% of rated power;
E-2XX SHEETS
Indicate that daylight sensing controls are configured to
completely shut off all controlled lights in the lighting zone
E2XX SHEETS,
SPEC 260923
NA C405.2.5
Additional controls -
Specific application
lighting controls
Identify spaces and lighting fixtures on plans that require
specific application lighting controls per this section
Indicate on plans that display and accent lighting, and display
case lighting are controlled independently from both general
area lighting and other lighting applications within the same
Indicate manual and automatic lighting control method
Yes C405.2.4.2
C405.2.4.3
Daylight zones -
Sidelight and toplight
NA C405.2.5 -
Items 1&2
Display and accent
lighting
Yes C405.2.4 Daylight responsive
controls
Yes C405.2.1
C405.2.1.1
Occupancy sensor
controls
Yes C405.2.2 Method of automatic
shut-off control
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
1/9/2016
Lighting, Motor, and Electrical Permit Checklist, Pg. 2 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Title: MADRONA SCHOOL REPLACEMENT Date 1/
Applicability
(yes,no,na)Code Section Component Compliance information required in permit documents
Location in
Documents
Building Department
Notes
NA C405.2.5 -
Item 3
Hotel/motel guest
rooms
Indicate method of automatic control - vacancy or captive key
control of all installed luminaires and switched receptacles in
guest room
NA C405.2.5 -
Item 4
Supplemental task
lighting
Indicate method and location of automatic shut-off vacancy
control for supplemental task lighting, including under-shelf or
under-cabinet lighting
Indicate on plans eligible non-visual lighting applications,
include sq. ft. area of each lighting control zone;
Indicate on plans that non-visual lighting are controlled
independently from both general area lighting and other lighting
applications within the same space;
Indicate method of manual lighting control and applicable
automatic lighting control
Indicate on plans that lighting equipment for sale or
demonstration are controlled independently from both general
area lighting and other lighting applications within the same
space;
Indicate method of manual lighting control and applicable
automatic lighting control
Identify on plans egress fixtures that function as both normal
and emergency means of egress illumination;E-2XX SHEETS
Provide calculation of lighting power density of total egress
lighting;
If total egress lighting power density is greater than 0.02 W/sq.
ft., indicate on plans egress fixtures requiring automatic shut-off
during unoccupied periods;
Indicate method of automatic shut-off control
Indicate on exterior lighting plans and fixture schedules the
automatic lighting control method, control sequence, and
locations served;
E-101, E-700
For building façade and landscape lighting, indicate automatic
controls shut off lighting as a function of dawn/dusk and fixed
opening/closing time;
For all other exierior lighting, indicate automatic controls shut off
lighting as a function of available daylight; include control
sequence that also reduces lighting power by at least 30%
between 12am-6am, or from 1 hour after closing to 1 hour
before opening, or based upon motion sensor
E-101, E-700
Yes C405.5.1
Exterior building
grounds lighting
controls
For building grounds fixtures greater than 100 watts, indicate on
plans whether fixtures have efficacy greater than 80 lumens or;
are controlled by motion sensor, or are exempt lighting per
C405.5.2
E-101, E-700
Indicate location(s) of master control switch(es) intended to
control multiple independent switches; circuit breaker may not
be used as a master control switch;
E-2XX SHEETS
Verify that no 20 amp circuit controlled by a single switch or
automatic control is loaded beyond 80%
PANEL
SCHEDULES,
FORTHCOMING
To comply with additional efficiency package option, indicate on
plans all interior lighting fixtures that are individually addressed
and provided with continuous dimming, or exception taken;
Include calculation of percent total installed interior lighting
power that is configured with required enhanced lighting control
functions (min 90% to comply with additional efficiency package
option)
If claiming lighting system commissioning exemption provide
supporting calculation;
Identify applicable commissioning documentation requirements
per Section C408 or eligibility for exception;SPEC 260500
Provide written procedures for functional testing of all automatic
controls and describe the expected system response SPEC 260500
C405.13
C408.3
Lighting system
functional testingYes
No C406.4 Enhanced digital
lighting controls
Yes C405.2.5
Area controls -
Master control
switches and circuit
power limit
NA C405.2.5 -
Item 5
Lighting for non-
visual applications
Yes C405.2.7 Exterior lighting
controls
NA C405.2.5 -
Item 6
Lighting equipment
for sale or
demonstration
Yes C405.2.5 -
Item 7
Means of egress
lighting
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
1/9/2016
Lighting, Motor, and Electrical Permit Checklist, Pg. 3 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Title: MADRONA SCHOOL REPLACEMENT Date 1/
Applicability
(yes,no,na)Code Section Component Compliance information required in permit documents
Location in
Documents
Building Department
Notes
INTERIOR LIGHTING POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
types, lamps, ballasts, and manufacturer's rated watts per
fixture;
E-700
Identify spaces eligible for lighting power exemption on plans
and in compliance forms; indicate the exception applied;
Identify lighting equipment eligible for lighting power exemption
in fixture schedule and in compliance forms; indicate the
exception applied;
Indicate that exempt lighting equipment is in addition to general
area lighting and is controlled independently
Yes C405.3 Exit signs Indicate location of exit signs on plans and rated watts per
fixture in lighting fixture schedule (maximum 5 watts per fixture)
E-2XX SHEETS, E-
700
NA C405.1 Lighting in dwelling
units - lamp efficacy
If high efficacy exception is applied to permanently installed
lighting fixtures in dwelling units, indicate in lighting fixture
schedule if lamps in fixtures are high efficacy per R404.1.
Calculate percentage of fixtures with high efficacy lamps in
project (min 75% to comply with exception).
NA C406.3
Reduced lighting
power density -
dwelling unit lamp
efficacy
For project with dwelling units, to comply with additional
efficiency package option indicate in lighting fixture schedule if
lamps in fixtures have efficacy rating of 60 lumens per watt or
more. Calculate percentage of fixtures with lamps that have this
efficacy rating (min 95% to comply with option).
Lighting Power Calculation - Indicate compliance path taken
Yes C405.4.2.1 Building Area Method
Complete required compliance forms – proposed wattage per
building area does not exceed maximum allowed wattage per
building area. Identify locations of building areas on plans
E-2XX SHEETS,
COMPLIANCE
FORMS
NA C405.4.2.2 Space-By-Space
Method
Complete required compliance forms – total proposed wattage
does not exceed maximum allowed wattage. Identify locations
of space types on plans, including retail display areas, lobby art
& exhibit display areas, and ceiling heights as applicable
Yes C406.3 Reduced lighting
power density
To comply with additional efficiency package option,
demonstrate in compliance forms that total connected interior
lighting wattage is 75% less than the total maximum allowed
lighting wattage via Building Area Method or Space-By-Space
Method
COMPLIANCE
FORMS
EXTERIOR LIGHTING POWER & EFFICACY
Include all luminaires in lighting fixture schedule; indicate fixture
types, lamps, ballasts, and manufacturer's rated watts per
fixture;
E-700
Identify exterior applications eligible for lighting power
exemption on plans and in compliance forms; indicate exception
Indicate that exempt exterior lighting is controlled independently
from non-exempt exterior lighting; include exception claimed for
each fixture or group of fixtures under exception category
Yes Table
C405.5.2(1)Exterior lighting zone Indicate building exterior lighting zone as defined by the AHJ COMPLIANCE
FORM
Yes C405.5.1 Exterior building
grounds lighting
For building grounds fixtures rated at greater than 100 watts that
are complying based on efficacy, indicate rated lamp efficacy (in
lumens per watt) in fixture schedule
E-700
Yes C405.5.2 Exterior lighting
power calculations
Complete required compliance form – proposed wattage for
exterior lighting plus base site allowed does not exceed
maximum allowed
COMPLIANCE
FORM
Yes C405.4.1
C405.4.1
C405.4.2
Total connected
interior lighting power
Yes C405.5.2
Total connected
exterior lighting
power
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
1/9/2016
Lighting, Motor, and Electrical Permit Checklist, Pg. 4 LTG-CHK
2015 Washington State Energy Code Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1 Revised August 2016
Project Title: MADRONA SCHOOL REPLACEMENT Date 1/
Applicability
(yes,no,na)Code Section Component Compliance information required in permit documents
Location in
Documents
Building Department
Notes
MOTORS & TRANSFORMERS
Yes C405.6 Electrical tranformers Include electrical transformer schedule on electrical plans;
indicate transformer size, efficiency, or exception taken E-600
NA C405.7
Dwelling unit
electrical energy
consumption
Indicate on electrical plans that each dwelling unit in Group R-2
has a separate electrical energy meter
Yes C405.8 Electric motor
efficiency
Include all motors, including fractional hp motors, in electric
motor schedule on electrical plans; indicate hp, rpm, rated
efficiency, or exception applied
E-3XX SHEETS
For luminaires in each elevator cab, provide calculated average
efficacy of combined fixtures that indicates efficacy is not less
than 35 lumens per watt;
Indicate rated watts per cfm for elevator cab ventilation fans do
not exceed 0.33 watts per cfm;
Indicate automatic controls that de-energize lighting and
ventilation fans when elevator is stopped and unoocupied for a
period of 15 minutes or more
NA C405.9.2 Escalators and
moving walks
Indicate escalators comply with ASME A17.1/CSA B44;
automatic controls are configured to reduce operational speed
to the minimum permitted when not in use
NA C405.9.3 Regenerative drive Indicate all one-way down or reversible escalators are provided
with a variable frequency regenerative drive
Identify all controlled and uncontrolled receptables on electrical
plans in each space in which they are required; include
receptacle configuration such as spacing between controlled
and uncontrolled, duplex devices, etc;
E-3XX SHEETS
Indicate on plans whether the method of automatic control for
each controlled receptable zone is by occupant sensor or
programmable time-of-day control
E-3XX SHEETS
If "no" is selected for any question, provide explanation:
Yes
No
N.A.
End of Lighting, Motor & Transformer Permit Documents Checklist
Yes C405.10 Controlled
receptacles
NA C405.9.1 Elevator cabs
Luminaire level lighting controls and enhanced digital lighting controls have not been implemented due to cost reasons.
The other energy efficiency options are achieved through efficiency in mechanical design. See mechanical compliance
forms.
The following information is necessary to check a permit application for compliance with the lighting, motor, and electrical requirements in the
Washington State Energy Code, Commercial Provisions.
1/9/2016