Mechanical Summary MECH-SUM
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised June 2013
Project Info Project Address
For Building Dept. Use
Applicant Name:
Applicant Address: #REF!
Applicant Phone: #REF!
Project Description
Briefly describe mechanical
system type and features.
TRUE
Compliance Option
Equipment Schedules
Cooling Equipment Schedule
Equip.
ID
Equip
Type Brand Name1 Model No.1
Capacity2
Btu/h
OSA CFM
or Econo?
SEER
or EER IPLV3
Econmizer
Option or
Exception6
Heat
Recovery
Y/N
See M003-M006
Heating Equipment Schedule
Equip.
ID
Equip
Type Brand Name1 Model No.1
Capacity2
Btu/h
OSA cfm
or Econo? Input Btuh Output Btuh Efficiency4
Heat
Recovery
Y/N
See M003-M006
Fan Equipment Schedule
Equip.
ID
Equip
Type Brand Name1 Model No.1 CFM SP1 HP/BHP Flow Control5 Location of Service
See M003-M006
Service Water Heating Equipment Schedule
Equip.
ID
Equip
Type Brand Name1 Model No.1
Input
Capacity
Sub-
Category EF7
See M003-M006
Drawings must contain notes requiring compliance with commissioning provisions per Section C408
Location of Service
(206) 779-3777
1/6/2017Madrona School
9300 236th St SW
Edmonds, WA 98020
Erik Olnon - Metrix Engineers
725 Powell Ave SW, Suite 100, Renton, WA, 98057
The following information is required to be incorporated with the mechanical equipment schedules on
the plans. For projects without plans, fill in the required information below.
1 If available. 2 As tested according to Table C403.2.3(1)A thru C403.2.3(8). 3 If required. 4 COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. 5 Flow control types: variable air volume (VAV), constant volume (CV), or variable speed (VS). 6 Economizer exception number per
Simple System Complex System Systems Analysis
Includes Plans
Date
Full mechanical system for new Madrona School. System includes boilers, pumps, air‐
to‐water heat pump, custom air handlers, VAV boxes and radiant floor heating.
Mechanical Permit Plans Checklist - Page 1 of 3 MECH-CHK
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised June 2013
Project Address Date 1/6/2017
Applicability
(yes,no,na)Code Section Code Provision Information Required
Location on
Plans
Building Department
Notes
Yes C403.2.1 Load calculations
Load calculations performed per ASHRAE Std 183 or equivalent per
Chapter 3 M003-M005
Yes C403.2.2 Equipment and system
sizing
Output capacity of heating and cooling equipment and systems do not
exceed calculated loads, note exceptions taken M003-M005
Yes C403.2.5 Minimum ventilation
Ventilation (natural or mechanical) provided per IMC; indicate mechanical
ventilation is capable of being reduced to minimum requirement per IMC M006
Yes
C403.2.3 &
C403.2.3.2 &
C403.2.12.1
Equipment minimum
efficiency
Provide equipment schedules or complete MECH-SUM tables with type,
capacity, efficiency, test standard (or other efficiency source) for all
mechanical equipment M003-M005
Yes C403.2.13 Electric motor efficiency
Provide equipment schedule with hp, rpm, efficiency for all motors; note
except.M003-M005
Yes C403.2.10 Fan power limitation
Fan system motor hp or bhp does not exceed limits per Table
C403.2.10.1(1)M002
Yes C403.2.10.3
& C403.2.13 Fractional hp fan motors Indicate fan motors 1/12 to 1 hp are ECM type or meet minimum efficiency
req.230513
N/A C403.2.3 Maximum air cooled chiller
capacity Indicate air-cooled chiller capacity does not exceed air-cooled chiller limit
N/A C403.2.1 Non-standard water-cooled
chillers
Full-load and NPLV values for water-cooled centrifugal chiller adjusted for
non-standard operational conditions
N/A C403.2.12.1.2 Centrifugal fan cooling
towers
Large capacity cooling towers with centrifugal fan(s) meet efficiency
requirements for axial fan open circuit cooling towers
N/A C403.2.3 Forced air furnace and unit
heaters Indicate intermittent ignition or IID, flue/draft damper & jacket loss
N/A C403.2.3.3 Packaged electric
heating/cooling equipment List equipment required to be heat pumps on schedule
N/A C403.2.3.4 Humidification
Indicate method of humidification (note requirements for systems with
economizer)
Yes C403.2.4.1 Thermostatic controls
Indicate locations of thermostatic control zones on plans, including
perimeter systems M3 Series
N/A C403.2.4.1.1 Heat pump supplementary
heat
Indicate staged heating (compression/supplemental) & outdoor lock-out
temp
Yes C403.2.4.2 Setpoint overlap (deadband)
Indicate 5°F deadband minimum for systems controlling both heating &
cooling 230993
Yes C403.2.4.3 Automatic setback and
shutdown
Indicate zone t-stat controls with required automatic setback & manual
override 230993
Yes C403.2.4.3.3 Automatic (optimum) start
Indicate system controls that adjust equip start time to match load
conditions 230993
Yes C402.4.5.2 &
C403.2.4.4 Dampers Indicate location of OSA, exhaust, relief and return air dampers; include
AMCA rated leakage and control type (motorized or gravity; note exceptions M3 Series
N/A C403.2.11 Heating outside a building Indicate radiant heat system and occupancy controls
N/A C403.2.4.5 Snow melt systems Indicate shut-off controls based on outdoor conditions
Yes C403.2.4.6 Combustion heating
equipment Indicate modulating or staged control 230993
N/A C403.2.4.7 Group R1 hotel/motel
systems
Indicate method for guest room automatic setback & set-up of 5°F
minimum
N/A C403.2.4.8 / 9 Group R2/R3 dwelling unit
systems
Indicate 5-2 programmable thermostats in primary spaces with minimum of
two setback periods; note exceptions taken
Yes C403.2.5.1 Demand controlled
ventilation Indicate high-occupancy spaces and systems requiring DCV M003
Yes C403.2.5.2 Occupancy sensors
Indicate spaces requiring occupancy-based system control and method; or
alternate means provided to automatically reduce OSA when partially 230993
N/A C403.2.5.3
Enclosed loading
dock/parking garage
ventilation
Indicate enclosed loading dock and enclosed parking garage ventilation
system activation and control method
Yes C403.2.5.4.1 Kitchen exhaust hoods
Indicate kitchen hoods requiring make-up air; indicate make-up air source
and conditioning method M3 Series
N/A C403.2.5.4.2 Laboratory exhaust systems
Indicate lab exhaust systems requiring heat recovery, method & efficiency;
or alternative method taken (VAV, semi-conditioned makeup, or CERM
calculation)
Yes C403.2.6.1 Energy recovery -
ventilation systems
Indicate ventilation systems requiring ER, method & efficiency; note
exceptions M003
N/A C403.2.6.2 Energy recovery -
condensate systems Indicate on-site steam heating systems requiring energy recovery
N/A C403.2.6.3 Energy recovery -
condenser systems Indicate remote refrig. condensers requiring ER and use of captured energy
Madrona School
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define print area in Excel prior to printing MECH-CHK pages.
GENERAL PROVISIONS
Equipment Sizing & Performance
HVAC System Controls & Criteria
Mechanical Permit Plans Checklist - Page 2 of 3 MECH-CHK
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised June 2013
Project Address Date 1/6/2017
Applicability
(yes,no,na)Code Section Code Provision Information Required
Location
on Plans
Building Department
Notes
Yes C403.2.12 Variable flow control -
fans/pumps
Indicate fan & pump motors requiring VF control & method (VSD or equiv
controls) M003
N/A C403.2.12.1 Variable flow control -
cooling towers Indicate cooling tower fans requiring variable flow control and method
N/A C403.2.12.2 Large volume fan systems
Indicate fan systems requiring airflow reduction based on heating and
cooling demand; or exception taken
N/A
C403.2.12.2 Single zone AC systems
Indicate method of cooling demand-based fan control for sys. > 110,000
btuh
Yes C403.2.4.10 DDC system capabilities
Identify all DDC system input/output control points and indicate capability
for trending and demand response setpoint adjustment 230900
Yes C403.2.7.1 &
C403.2.7.3 Duct construction Indicate all ductwork constructed and sealed per IMC, C402 leakage
requirements and IBC vapor retarder requirements 233113
Yes C403.2.7.3.1-3Duct pressure
classifications Identify location of low, medium and high pressure ductwork on plans 233113
Yes C403.2.7.3.3 High pressure duct leakage
test
Indicate high pressure duct leakage testing requirements on plans; provide
test results to jurisdiction when completed 233113
Yes C403.2.7.1 / 2 Duct insulation Indicate R-value of insulation on ductwork 230700
Yes C403.2.8 Piping insulation Indicate R-value of insulation on piping 230700
Yes C403.2.8.1 Piping insulation exposed to
weather Indicate method of protection from damage/degredation 230700
N/A C403.3 Qualifying single zone
systems
Verify unitary or packaged equipment does not exceed capacity limits,
does not have active humidifcation or simultaneous heating/cooling
N/A C403.3 Qualifying 2-pipe heating
systems Verify 2-pipe heating-only system does not exceed capacity limits
N/A C403.3.2 Hydronic system controls Refer to Complex Systems Section C403.4.3
N/A C403.3.1 Air economizer required
Indicate cooling systems requiring economizer controls; note in equip
sched.
N/A C403.3.1.1.1 Air economizer capacity Indicate modulating OSA control capability up to 100% OSA, or exception
N/A C403.3.1.1.3 Air economizer high limit
controls Indicate high limit shut-off control method per Table C403.3.1.1.3(2)
N/A C403.1.1.2 Integrated air economizer
operation
Indicate capability for partial air economizer operation for systems with
capacity > 65,000 btuh
N/A C403.3.1 Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with
exception(s)
Yes C403.4.1 Air economizer required
Indicate cooling systems requiring economizer controls; note in equip
sched.M003-M006
Yes C403.4.1.4 Economizer heating system
impact
Verify control method of HVAC systems with economizers does not
increase building heating energy usage during normal operation 230993
Yes C403.4.1.3 Integrated economizer
operation
Indicate capability for partial economizer operation for air or water econo
systems 230993
N/A Moved Water economizer capacity
Indicate water econo capable of 100% cooling capacity at 50°F db/45°F wb
OSA
N/A C403.4.1.2 Water economizer
maximum pressure drop
Indicate precooling coils and heat exchangers do not exceed pressure
drop limit
N/A C403.3.1 Air economizer exceptions
Indicate eligible exception(s) taken and provisions to comply with
exception(s)
Madrona School
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define print area in Excel prior to printing MECH-CHK pages.
GENERAL PROVISIONS, CONTINUED
Qualifying Systems
Simple System Economizers
COMPLEX SYSTEMS
Ducting Systems
Piping Systems
SIMPLE SYSTEMS
HVAC System Controls & Criteria, Continued
Complex System Economizers
Mechanical Permit Plans Checklist - Page 3 of 3 MECH-CHK
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3 Revised June 2013
Project Address Date 1/6/2017
Applicability
(yes,no,na)Code Section Code Provision Information Required
Location on
Plans
Building Department
Notes
Yes C403.4.2 &
C403.2.12 Variable flow control - fans Indicate fans requiring variable flow control and method M003-M006
Yes C403.4.2.1 VAV fan static pressure
sensors
Indicate sensor locations on plans; include at least one sensor per major
duct branch 230993
Yes C403.4.2.2 VAV fan static pressure
setpoint
Indicate fan system static pressure setpoint based on zone requiring most
pressure 230993
Yes
C403.4.5 VAV systems serving multi-
zones
Indicate supply air systems serving multiple zones that are required to be
VAV, method of primary air control, and zones served; note exceptions
taken M003-M006
Yes C403.4.5.4 VAV system supply air reset
Indicate controls that automatically reset supply air temp in response to
loads 230993
N/A C403.4 Large capacity cooling
systems
Indicate method of multi-stage or variable control for building cooling
system capacity > 300 tons
N/A C403.4.7 Hot gas bypass limitation Indicate cooling equipment unloading or capacity modulation method
Yes C403.4.3 Large capacity boiler
systems Indicate multi-stage or modulating burner for single boilers > 500,000 btuh 235216
Yes C403.4.3 Boiler sequencing Indicate automatic controls that sequence operation of multiple boilers 230993
Yes C403.4.3.5 Chiller / boiler plant pump
isolation
Indicate capability to automatically reduce overall plant flow and shut-off
flow through chillers & boilers when not in use 230993
Yes
C403.4.2 &
C403.4.3.6
Variable flow control -
pumps Indicate pumps requiring variable flow control & method M003
N/A C403.2.12.1
& C403.4.4
Variable flow control -
cooling towers Indicate cooling tower fans requiring variable flow control and method
Yes C403.4.3.4 Hydronic system part load
controls
Indicate heating & chilled water systems have the capability to automatically
reset supply water temp AND reduce flow by ≥ 50% for systems > 300,000 230993
Yes C403.4.3.2 Two-pipe changeover
systems
Indicate deadband, heating/cooling mode scheduling and changeover
temperature range 230993
N/A C403.4.3.3.1 Water loop heat pump -
deadband
Indicate capability of central equipment to provide min. 20°F water supply
temp deadband between heat rejection and heat addition modes
N/A C403.4.3.3 Water loop heat pump -
heat rejection
Provide heat exchanger that separates cooling tower and heat pump loop
in Climate Zone 5
N/A C403.4.3.3.3 Water loop heat pump -
isolation
Indicate 2-way isolation valve on each heat pump and variable flow control
for systems with total pump power > 10 hp
N/A C403.4.6 Condenser water heat
recovery Indicate system provided to pre-heat service water and efficiency
N/A C403.5 Cooler / freezer - anti-sweat
heaters
Indicate w/sf & control method for walk-in cooler/freezer door anti-sweat
heaters
N/A C403.5 / 6 Cooler / freezer - evaporator
and condenser fans Indicate motor type for evaporator and condenser fans < 1 hp
Yes C404.2 Water-heating equip min.
efficiency
Provide equipment schedule or complete MECH-SUM table with type,
capacity, efficiency, test standard (or other efficiency source) M003
Yes C404.3 Temperature controls Indicate temperature controls have required setpoint capability 230993
Yes C404.4 Heat traps
Indicate piping connected to equipment have heat traps on supply &
discharge M003
N/A C404.5 Insulation under water
heater Indicate R-10 insulation under tank
Yes C404.6 Service water piping
insulation Indicate R-value of insulation on piping; note exceptions taken 230700
Yes C404.7 / 8 Circulation systems and
heat trace shut-off
Indicate shut-off capability based on occupancy and periods of limited
demand 230993
N/A C404.9 Group R-2 service hot water
meters
Indicate method of usage metering for dwell. units served by central HW
system
N/A C404.10.1 Pool heating equip min.
efficiency
Provide equipment schedule or complete MECH-SUM table with type,
capacity, efficiency, test standard (or other eff. source); heat pump heaters
≥ 4 COP
N/A C404.10.1 / 2 Pool heater on / off controls
Indicate automatic on/off control based on scheduling & accessible on/off
switch on heater that operates independent of thermostat setting; or
N/A C404.10.3 Pool covers Indicate vapor retardant cover and insulation rating as required
N/A C404.10.3 Pool assembly insulation Indicate rating of insulation on sides and bottom of pools heated to > 90°F
N/A C404.10.4 Heat recovery
Indicate method, exhaust air temperature reduction and recovered energy
use
The following information is necessary to check a mechanical permit application for commercial provision compliance with the 2012
WSEC. NOTE: Define print area in Excel prior to printing MECH-CHK pages.
COMPLEX SYSTEMS, CONTINUED
Specific System Requirements
SERVICE WATER HEATING
Pools & In-Ground Permanently Installed Spas
Service Water Systems
Madrona School