City of Edmonds
PLAN REVIEW COMMENTS
' BUILDING DIVISION
(425) 771-0220
DATE: March 12, 2008
TO: Miroslaw and Bogumila Kanczugowski
2381177 TH Place W.
Edmonds, WA 98026
FROM: Jenny Readwin, Plans Ex 'n
RE: Plan Check # 2007-1021
Project: Detached Garage
Project Address: 23811 77th Place W
During re -review of the above noted application, it was found that the following information,
corrections, or clarifications are needed. Please redline plans or submit two (2) sets of revised
plans/documents (affected sheets only) with a written response to each of the items below to a
Permit Coordinator.
1) ok
2) 3/12/08 Orikinal site plan showed the house and earake 5' apart Now it shows 3. This
changes the requirements For the house now you can only have maximum 12"eaves and
they must be protected with a listed tested l HR Assembly (see attached sample). To do this
the eave must be soffrtted and protected. Provide detail of proposed eave protection with eave
dimensions. This will also block some of the ventinie so also provide attic ventilation
calculations. Additional vents may be required. Because the work is done on a separate
buildink then_a separate building permit would be required. Contact a permit coordinator for
application requirements. 2/21/08 need 1 -hr listed and tested assembly on the plans. See
attached samples. Based on R302 because the house and garage are not 6' apart, the garage wall
will need to be one-hour fire -resistive rating with exposure from both sides and no openings are
permitted in this wall with maximum of 4" eaves. See attached 1 -hr listed and tested assembly.
Note on plans.
3) 3/12/08 This still does not -appear to be addressed. Please provide written response. 2121108
New Based on the picture in the file it appears that the foundation for a 2 car garage was
poured. Please specify if this is to be altered or if it will be completely removed and a new
foundation will be poured. Because we were not present to inspect before the concrete was
poured, if the existing is to be altered, special inspection by a Washington State Licensed
Engineer will be required to verify the structural integrity of the foundation. Also based on the
pictures it does not appear to have all the required holdowns, so retro -fit holdowns will be
required and special inspection is required for epoxy or expansion anchor holdowns.
4) Ok
5) ok
6) ok
7) Ok
FIRE RESISTANCE DESIGN MANUAL 133
GA FILE NO. RC 2601
GENERIC
SUM WALLBOARD, WOOD JOISTS, ROOF COVERING
Base layer Sla" type psum wallboard applied at right angles to 2 x 10 wood joists 24'
o.c. with 1114" Type S drywall screws 24" o.c. Face layer 51a. type X gypsum
wallboard or gypsum vene a applied at right angles to joists with 17le Type W or
S drywall screws 12" o.c. at j d intermediate joists and 1112" Type G d l
screws 12" o.c. placed 2" back on eithe f end joints. Joints off ase
layer joints. Wood joists supporting 112' pp
ri > led at right angles
to joists with 8d nails. Appropriate roof cover ovides one hour fire
resistance protection for framing, i russes.
GA FILE NO. RC 2602 1 1 ' GENERIC
WOOD TRUSSES, GYPSUM WALLBOARD
Base layer 51s" type X gypsum wallboard applied at right angles to wood roof trusses 24"
o.c. with 1114" Type W or S drywall screws 24" o.c. Face layer Ns" type X gypsum
wallboard or gypsum veneer base applied at right angles to trusses with 171a" Type W or
S drywall screws 12" o.c. at joints and intermediate trusses and 1112" Type G drywall
screws 12" o_c. placed 2" back on either side of end joints. Joints offset 24" from base
layer joints. Wood trusses supporting 112" wood structural panels applied at right angles
to trusses with 8d nails. Appropriate roof covering. Ceiling provides one hour fire
resistance protection for trusses.
1 HOUR
FIRE
Approx. Ceiling
Weight: 5 psf
Fire Test: FM FC 172, 2-25-72;
4rol_ ITS, 8-6-98
1 HOUR
FIRE
Approx. Ceiling
Weight: 5 psf
Fire Test: FM FC 172, 2-25-72;
ITS, 8-6-98
more aeraffea inrormarion on
ROOF -CEILING SYSTEMS
GA FILE NO. RC 2501 PROPRIETARY*
1 HOUR
FIRE
EL ROOF TRUSSES, RESILIENT OR RIGID CHANNELS,
`
HERMAL INSULATION, GYPSUM WALLBOARD
.
One layer SIB' proprie type X gypsum wallboard or gypsum veneer base applied at right��
'
angles to resilient o id furring channels with 1118' Type S drywall screws 12" o.c.y,
"ea`
Channels spaced 12" o. hen insulation is used or 16" o.c. when no insulation is used.
f `
Gypsum board end joints hod with screws 12" o.c. to additional pieces of channel
'
60" long located 3" back on e r side of end joint. Resilient channels applied at right
'''
a '
angles to bottom chord of pitche parallel chord steel trusses 48" o.c. with 112" Type
S-12 screws or rigid furring channe cured to the bottom chord of each truss With"
double -strand wire saddle ties (refer to !ng channel manufacturer for rneikimum
spans). Optional glass fiber or mineral fibe' tt or loose fill insulatia �o ed directly
over gypsum board. Trusses supporting metal deck panels doy'eled by 11z" regular
gypsum sheathing either loose laid or adhesively or cha ga,16§aRached to roof deck.
Any thickness polyisocyanurate foamed plastic; poly ° % foamed plastic; or mines[
fiber or glass fiber insulation boards laid over gy she ' and covered by a Class
A, 6, or C roof covering.
PROPR Y GYPSUM BOARD
Approx. Ceiling
National Gypsum Company - sh" Gold Bond® Brand -SHIELD CT"'
Weight: 3 psf
Gyps Wallboard
Fire Test: UL 83501, 01NK49664,
9-5-02,
UL Design P540
GA FILE NO. RC 2601
GENERIC
SUM WALLBOARD, WOOD JOISTS, ROOF COVERING
Base layer Sla" type psum wallboard applied at right angles to 2 x 10 wood joists 24'
o.c. with 1114" Type S drywall screws 24" o.c. Face layer 51a. type X gypsum
wallboard or gypsum vene a applied at right angles to joists with 17le Type W or
S drywall screws 12" o.c. at j d intermediate joists and 1112" Type G d l
screws 12" o.c. placed 2" back on eithe f end joints. Joints off ase
layer joints. Wood joists supporting 112' pp
ri > led at right angles
to joists with 8d nails. Appropriate roof cover ovides one hour fire
resistance protection for framing, i russes.
GA FILE NO. RC 2602 1 1 ' GENERIC
WOOD TRUSSES, GYPSUM WALLBOARD
Base layer 51s" type X gypsum wallboard applied at right angles to wood roof trusses 24"
o.c. with 1114" Type W or S drywall screws 24" o.c. Face layer Ns" type X gypsum
wallboard or gypsum veneer base applied at right angles to trusses with 171a" Type W or
S drywall screws 12" o.c. at joints and intermediate trusses and 1112" Type G drywall
screws 12" o_c. placed 2" back on either side of end joints. Joints offset 24" from base
layer joints. Wood trusses supporting 112" wood structural panels applied at right angles
to trusses with 8d nails. Appropriate roof covering. Ceiling provides one hour fire
resistance protection for trusses.
1 HOUR
FIRE
Approx. Ceiling
Weight: 5 psf
Fire Test: FM FC 172, 2-25-72;
4rol_ ITS, 8-6-98
1 HOUR
FIRE
Approx. Ceiling
Weight: 5 psf
Fire Test: FM FC 172, 2-25-72;
ITS, 8-6-98
more aeraffea inrormarion on