2012-0688 Las Brisas Fireplace.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: August 21, 2012 TO: Villa’s Construction Email: villasconstruction@gmail.com FROM: Leif Bjorback, Assistant Building Official RE: Plan Check: 2012-0688 Project: Las Brisas Fireplace th Project Address: 201 5 Ave S Suite 101 During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses as to where the changes can be found on the plans, and submit revised plans/documents to a permit coordinator in the Development Services Department. Thank you. 1.The gas burner appliance must be listed and labeled by an approved agency such as ANSI or CSA for the use of the appliance. Please provide the listing and associated specifications for review. An alternate to this would be to provide a design that is stamped and signed by a Washington State licensed mechanical engineer. IFGC 301.4 2.Provide the listing and specifications for the exhaust fan and hood. Include the listing agency, CFM’s, and installation instructions. Show which exterior wall the duct terminates through (west or south?) IFGC 304.1