Loading...
2014-0616 Rundorff deck addition - HO.pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: July 2, 2014 TO: Lawrence Rundorff rundorff@yahoo.com FROM: Chuck Miller, Plans Examiner RE: Plan Check: BLD2014-0616 Project: Rundorff deck addition Project Address: 7520 Braemar Drive During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. On sheet 1: 1.Clarify the callout for the preservative-treated 2x8s installed at 24 inches on-center to be used as joists spanning 13 feet with a 1 foot overhang. They appear to be over spanned, fail in bending, and deflect beyond that allowed per Table R301.7. Include the size, species, and grade of the proposed framing member in the response. (The north end of the existing deck joists appear to be supported by a beam that could be used to provide mid span support for the proposed joists. The size, species, grade, and span (the distance between each supporting posts) of the existing beam would be required for the determination of its ability to support the additional load.) 2.Clarify the callout for the 16x16x12 isolated footing to be used to support the center of the three posts below the proposed 4x12 beam under the north end of the new deck joists. It appears to be undersized for the loads anticipated at that location by the represented construction. (If the existing beam is used to provide support for the south end of the new portion of the deck, the load at the center post may be significantly diminished and the size of the proposed isolated footing may be sufficient.) 3.Clarify the callout for the (2)2x8s to be used to support the south end of the new 14 foot long deck joists. They appear to be over spanned, fail in bending, and the overhang deflects beyond that allowed per Table R301.7. Include the size, species, and grade of the proposed framing member in the response. (If the existing beam is used to provide support for the south end of the new portion of the deck, the load on the ‘doubled’ beam may be significantly diminished (or eliminated) and no change would be necessary.) 4.Clarify the callout for the existing 4x12 to be used to support the west end of the (2)2x8s supporting the south end of the new 14 foot long deck joists. It appears to be over spanned, fails in bending, and deflects beyond that allowed per Table R301.7. Include the size, species, and grade of the proposed framing member in the response. (If the existing beam is used to provide support for the south end of the new portion of the deck, the load on the existing beam may be significantly diminished (or eliminated) and no change would be necessary.) On sheets 1 and 4: 5. Clarify the callout for the 3/8 inch diameter 4 inch long ‘bolts’ with washers to be used to attach the ledger to the house. Bolts are threaded fasteners that pass through the materials to be connected/joined and have a nut that is tightened and keeps them in place. Typically, lag screws are used for the type of connection proposed due to the difficulty of attaching the nut required for a bolted connection. If a lag screw is to be used, it must be a minimum of ½ inch in diameter per Table R507.2 and the National Design Specification for Wood Construction (NDS). Page 2 of 2