Loading...
2016-0179 Therrell (Kearsley).pdf City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 DATE: April 4, 2016 TO: Robin Kearsley r@kearlsleyhomes.com FROM: Andrew Gahan, Plans Examiner RE: Plan Check: BLD2016-0179 Project: Therrell Remodel/Addition Project Address: 8609 Talbot Road During a review of the plans by the Building Division for the above noted project, it was found that the following information, clarifications, or changes are needed. A complete review cannot be performed until the revised plans/documents, including a written response indicating where the ‘clouded’ or otherwise highlighted changes can be found on the revised plans, have been submitted to a Permit Coordinator. Reviews by other divisions, such as Planning, Engineering, or Fire, may result in additional comments. Sheet A1.0 1.The table of contents listed on sheet A1 does not coincide with the sheets submitted. Please review and revise for accuracy. 2.As a courtesy: It appears that the homeowners name is spelled incorrectly under the project directory section. Sheet A3.0 st 3.Please provide a roof truss/top of shearwall connection at the interior walls between the 1 nd and 2 overhead garage doors. Additionally, note on the plans that the truss(es) used to transfer that lateral load to the shearwalls below is (are) structurally adequate to transfer the required load 4.The new 3068 windows at each side of the front door should be tempered per IRC R308.4.2. 5.The permit application submitted with the plans states that the windows throughout the structure are to be replaced. After reviewing the proposed plans in comparison with the original drawings, it appears there are a few new windows, and that many of the windows to be ‘replaced’ are also increasing in size thus decreasing the available length of shear wall to transfer the required wind and seismic loads. Especially in the area of the Game Room and Exercise Room. Please submit lateral calculations to support the proposed configuration. The calculations are to be stamped and signed by an engineer licensed to practice in the State of Washington. 6.Please specify the structural members to be used to frame the front porch roof. Will it be comprised of trusses or stick-framing? If trusses, will it utilize a girder truss? If stick- framed, what connections will be used? Sheet A4.0 7.The Master Bathroom requires an exhaust vent per IRC Table M1507.4, as amended by the State of Washington, in addition to the exhaust vent shown within the toilet room. 8.Similar to comment #5 above, the permit application submitted with the plans states that the windows throughout the structure are to be replaced. After reviewing the proposed plans in comparison with the original drawings, it appears there are a few new windows, and that many of the windows to be ‘replaced’ are also increasing in size thus decreasing the available length of shear wall to transfer the required wind and seismic loads. Especially in the area of the Kitchen and Dining Room. Please submit lateral calculations to support the proposed configuration that are stamped and signed by an engineer who is licensed to practice in the State of Washington. 9.Please provide a detail at the angled portion of the deck stairs to show how the ST18 straps will support the stair stringers to help guide proper plan review, construction and inspection. Sheet A6.0 10.Detail 5 shows that the bottom of footing is 16” below finished grade. The frost protection depth in Edmonds is 18” minimum below finished grade. Please revise the detail. 11.Section A-A specifies 2x6 studs @ 24” o.c. Everywhere else, the studs are called out at 16” o.c. Please revise for consistency. Sheet A7.0 12.Please revise/update the General Notes to exclude references to earlier Code editions such as in notes 10 and 14. 13.Remove the 2009 VIAQ reference from General Note 29. 14.Please update Mechanical and Energy (M&E) Note 7 to show that Edmonds is in Climate Zone ‘Marine 4’. 15.Remove M&E Notes 8 and 10. 16.Revise M&E Note18 to reference the 2012 WSEC rather than the VIAQ. Sheet S1.0 17.As a courtesy: It appears the homeowner’s name is spelled incorrectly on the calculation sheets provided. Page 2 of 2