EE-1.pdfEagle Eye Consulting Engineers, PS ISO Box 523 Ofafla, WA 98359 hoytjeter@centurytel.net 253 857-4151 Fax 253 857-5759 To: Theresa Umbaugh City of Edmonds Edmonds, 0 Re: Bui Residence 16105 75th PIace West Edmonds, 0 Plan Review # 05-564 EECE # ED 05-72 Structure Area S.F. Lower floor 1051 Main floor 2988 LJpper floor 2043 Total 6082 Garage 840 Total 6922 Deck 876 Grand total 7798 The above referenced project is in the process of plan review for compliance with Edmonds ordinances and applicable codes. The following comments, deficiencies/corrections must be addressed prior to completion of plans review and subsequent issuance of permits. Provide revised plans and calculations along with a written response to each of the items listed below to facilitate a shorter back -check time. SCOPE OF REVIEW The scope of this review is for the structural and non-structural requirements of this project- All roject Ail features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. General Sheet 10 ELEVATIONS: 2. Please provide requirement for the attachment of the concrete tile. R905.3.5 And 905.3.7 Sheet 4 LOWER FLOOR PLAN: 3. Please modify note 18C to state 72" and not 70 inches for the waterproofing. 8307.2 Sheet S MAIN FLOOR PLAN: 4. Please modify note 18C to state 72" and not 70 inches for the waterproofing. R307.2 5. Please provide information for the fireplace. It is being placed next to the house on the terrace. The chimney must extend past combustible material. The elevation does not show this fireplace. A wood burning fireplace requires this information to be shown. Please add all pertinent information per chapter 10 of the IRC. Sheet 8 UPPER FLOOR PLAN: 5. Please label the window at the bathtub to be safety glazed. The master bedroom is labeled but not the other bathroom on this floor. R308.4 7. 1 was unable to find where the attic access was specified on the drawings. Please clarify location and size. R807.1 8. Please add a fan in where the bath tub is located. One is also required at this location. R303.3 Page 3 of 5 9. Please provide detail on the drawing for the guards required for the opening in the floor diaphragm. R312. 10. Please modify note 18C to state 72" and not 70 inches for the waterproofing. R307.2 Sheet 9 ROOF FRAMING PLAN: 11. Please show size and location of the required roof vents. R806 STRUCTURAL COMMENTS General 12. It appears based off the analysis submitted the roof framing was not included in the seismic analysis. All that is shown is for the upper level, main level and the basement. Please clarify the analysis when resubmitting. IBC 1617.5.1 13. Roof framing has concrete tile. Please clarify how this was accounted for in the seismic analysis. It appears this has not been included in the design. Please clarify on the response and give a break down of the dead loads used. 14. EOR please justify exposure B used for this structure. Since the structure is located on the Puget Sound it appears by definition exposure B is not correct but exposure C shall be used. Please justify. IBC 1.609.4 15. Based off the seismic analysis the factors were determined based off the zip code and not the soil report. This is not conservative for this structure based off report prepared by LSI Adapt. Please submit letter from the geotechnical engineer to justify seismic design parameters used in the design. IBC 1615 16. It does not appear 70 Psf traffic loading as recommended by the geotechnical engineer was accounted for in the design of the retaining walls. This will apply for this structure. Please clarify on the response. Sheet 1.1 SITE PLAN: 17. Please provide detail on the drawing for the retaining wall shown. All that is stated is 30 inches wall per sheet 2.1. There is not any retaining wall on this sheet. Please clarify on the response. IBC 1806. Sheet 7 UPPER FLOOR FRAMING PLAN: 18. Please provide analysis for the typical header of (2) 2x10 HF as noted in general note number 3. Analysis submitted appears not to address this. IBC 106.3.3 Page 4 of 5 19. Please provide a detail for the post that supports the 5-118X18 and 3-112X11-7/8 beam. How is this to be framed? Is the glu-lam notched at this location? Please provide analysis and details for this condition. IBC 2304.9.7 20. Please specify the hanger size to use at the deck joist. IBC 23 04.9.6 21. Check analysis for (2) 2x10 at the media room shows this will not support the loads. Also this is located at the window. Based off the span the beam will deflect and the opening for the window may not work. Please provide analysis for this header to justify. IBC 106.3.3 Sheet 9 ROOF FRAMING PLAN: 22. Please specify the B412 hanger for each side of the 4X12. beam.. It is only specified on one side. IBC 106.3.3 23. Please specify the post size and the required connection. All that I was able to find was the note to post down. All posts are required to have positive connections specified or detailed on the drawings. R407.3 Sheet S 1.1 DETAILS: Sheet S 1.2 DETAILS: 25. Detail 12: Please specify the required embedment for the threaded rod into the blocking piece. All that is specified is per manufacture but the size of the bolt and the required embedment should be specified. I assume a lag bolt is going to be used at these locations. ENERGY COMMENTS Prescriptive method used. No comments at this time VENTILATION AND INDOOR AIR QUALITY COMMENTS Sheet 8: Page 5 of 5 26. Based off the number of bedroom and the square footage it appears the whole house fan CFM size does not meet table 3-2. All bedrooms must be used when determining the minimum and maximum required ventilation. Please verify and modify accordingly. 27. Please specify the required fan for the Bathroom on this level. Additional corrections may be required following receipt of corrections and additional information as requested. Your plans are being reviewed concurrently with the Building Department, Fire Department, Zoning Department and Public Works Engineering. Changes, clarifications or additional corrections may be required subsequent to the Building Department plan review when comments are received from the other concerned departments. Should you have any inquiries regarding this letter, please contact Hoyt Jeter at (253) 857.41.51. between 8:00 a.m. and 5:00 p.m. By: Hoyt Jeter, P.E. President