Loading...
Response to BLDG Comments 2.pdffre e m a 00�� architects>connect, March 611, 2018 /�P Sv City of Edmonds 9�r *41? /r e 121 5th Avenue N cr�rNG Edmonds, WA 98020 ��FNAgR 8 MOA�� RE: Plan Check: BLD2017-1793 — 2nd Review Project Address: 540 511 Avenue 5 Project lust Like Home Laundry Tenant Improvement Scope: Remove/add non -bearing interior walls to create/reconfigure spaces — nonseparated B occupancy group —13 occupants — assumed VB construction — NFPA 13 sprinkler system — mechanical, fire sprinkler, fire alarm, etc. under separate permits On sheet A2,0 — Partial Main Floor: Partial Main Floor Plan, Partial Reflected Ceiling Plan, Equipment Info & Details: 6. Light Fixture Schedule — Note 3 — Indicate on the plans the required occupancy sensor controls per WSEC C405.2.1 for the lighting in the following spaces: • Utility • Bath Dryers Access On Sheet A2.0, under "Light Fixture Schedule", Note #2 has been modified to read as follows: "MANUAL LIGHT SWITCHING, U.O.N. INSTALL OCCUPANCY SENSOR CONTROLS PER WSEC C405,2.1 FOR THE LIGHTING IN UTILITY, BATH & DRYERS ACCESS." On the provided 2015 Washington State Energy Code (WSEC) 'Compliance Forms for Commercial Buildings including R2, R3, R4 over 3 stories and all R1' worksheets: 7. On the'Interior Lighting — Building Area Method — LTG-INT-BLD — worksheet a. Clarify the use of the 'Building Area Method' for the proposed lighting installation. For lighting alterations where less than 50% are being replaced, the 'Space -By -Space Method' is to be used - see page 3 of these comments. PER office 14410 SE Petrovitsky Rd, Suite 206 / Renton, Washington 98058 mail PO Box 19296 / Seattle, Washington 98109-1296 Freeman Architects tel 206 282 8245 / fax 206 283 0895 / web www.freemanconnects,com b. In the'Maximum Allowed Lighting Wattage' portion of the form —Clarify the indicated 'Allowed Watts per ft2, for the 'Laundromat' area. It does not appear to correspond with that found in the current version of the WSEC. Provide in response to the above plan review comment a completed 'Interior Lighting — Space -By -Space Method'— LTG-INT-SPACE — (preferably the'Revised Nov 2017 version found here ). Since the 'total proposed watts' of the proposed lighting installation is prohibited from exceeding the 'allowed watts' of the existing installation, 'existing' fixtures must be removed/reduced in wattage to accommodate the added 'Type C' light fixtures — see page 4 of these comments. The resulting lighting plan can then be represented on sheet'A2.0' - Plan'1' — Partial Main Floor Reflected Ceiling Plan. "Interior Lighting — Space -By -Space Method" — LTG -IN -SPACE worksheet, "Revised Nov 2017 version" is used. See attached worksheets. Type B and Type C existing fluorescent fixtures are being replaced with new LED lighting to meet "Maximum Allowed Lighting Wattage", which has also been modified. See LIGHT FIXTURE SCHEDULE on Sheet A2.0 and attached worksheets. office 14410 SE Petrovitsky Rd, Suite 206 / Renton, Washington 98058 mail PO Box 19296 / Seattle, Washington 98109-1296 Freeman Architects tel 206 282 8245 / fax 206 283 0895 / web www.freemanconnects.com