wall 1.pdfDATE: April 6, 2006 City of Edmonds PLAN REVIEW COMMENTS BUILDING DIVISION (425) 771-0220 TO: Clayton Yakubow Fax (425)355-3347 FROM: Jenny Readwin, Plans Examiner RE: Plan Check # 06-116 Project: Heath Retaining Wall Project Address: 8125 Frederick Place During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. 1) Provide stamped and signed structural calculations and detail for proposed retaining wall. Per our attached handout this is a minimum permit submittal requirement. This application requires peer review and since peer review is at the expense of the applicant we will not send it out for review until we receive structural calculations. 2) Special inspections are required for the following. Complete the enclosed special inspection agreement signed by the owner, the general contractor and the special inspector and submit to the City for approval prior to issuance. • Excavation, grading and site preparation • Soil bearing and Sonotube installation • Placement of fill and compaction • Retaining wall construction • Geogrid installation • Retaining wall drainage • Temporary and final erosion control Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the above items to a Permit Coordinator.