wall 2.pdfoV EDS City of Edmonds ,, ...,e,.. PLAN REVIEW COMMENTS BUILDING DIVISION �St, 189 (425) 771-0220 DATE: *prif-6, 006 ,,�Uy�_q �t 2ZO(P TO: Clayton Yakubow Fax (425)355-3347 FROM: Jenny Readwin, Plans Exami RE: Plan Check # 06-116 Project: Heath Retaining Wall Project Address: 8125 Frederick Place During review of the above noted application, it was found that the following information, corrections, or clarifications are needed. 1) Calculations provided need to be stamped and signed by engineer of record. Provide stamped and signed structural calculations and detail for proposed retaining wall. Per our attached handout this is a minimum permit submittal requirement. This application requires peer review and since peer review is at the expense of the applicant we will not send it out for review until we receive structural calculations. 2) Ok 3) New: Site plan says wall will he 3' tall, calculations are for 4', and the detail in the geotech report goes up to 6'. Please clarify and coordinate plans and calculations. Per note by the planning department wall can not exceed 3' above original grade. Please redline plans or submit two (2) sets of revised plans/documents (affected sheets only) with a written response to each of the above items to a Permit Coordinator.