1749_001r"Z3U3 ra),y City of Edmonds JUL 16 2019 o E3u!inMc orrnRTn4Erv1 PLAN REVIEW COMMENTS C1 IN OF en BUILDING DIVISION CSC. g9° (425) 771-0220 DATE: July 1, 2019 TO: Tom Budinick Email: tbudinick0mbudinickassoc.com FROM: Leif Bjorback, Building Official RE: Plan Check: BLD2019-0702 Project: Restaurant expansion into adjacent suite Project Address: 190 Sunset Ave During review of the plans for the above noted project, it was found that the following information, clarifications or changes are needed. Please provide written responses to each comment, and submit revised plans/documents to a permit coordinator in the Development Services Department. 1. A complete review by the Building Division cannot be performed until the following documents are provided and changes made: Provided a Floor plan for the enure ' a, y� y p In addition to the floor plans already provided for the work area, provide a partial restaurant shown on page A_01, r r- ,including occupant loads as provided floor plan including the layout of the entire restaurant. The layout does not need to in the original TI in 2016: BDL2016-0222 show extensive detail of the existing unchanged areas except for the square footages and occupant loads of each space, and the overall egress system for the suite. °. Completed on "'�' A.°1 Label the use of each room or space. c. The occupant load clacs are shown "C,.� On sheet a01, provide new occupant load calculations, showing a breakdown :table on A.M. Itemized by existing restaurant space and proposed TI including each room or space, with a proposed occupant load total for the entire space. The total occupant load for the entire restaurant is662. interior of the restaurant. It is advisable for you to reference the calculations for the previous work completed under permit BLD2016-0222 as applicable. d. Lighting design completed for the d: Due to the alterations and the partial change of occupancy/use of this project, a existing space (E.01) and the TI E.01 design was lighting design will be required for the complete restaurant, complete with fixture proposed (E.02). approved in2016: BDL2016-0222. wattages and lighting controls sufficient to show compliance with WSEC C405. Energy forms are attached to the -e. Provide energy forms for Lighting in support of the required lighting plan in item (d) resubmiltal set above. Thank you, Leif Bjorback, Building Official City of Edmonds (425) 771-0220 Lei f.biori back(u edmondswa.sov Page 1 of 1 0 %",