Laserfiche WebLink
<br /> <br />MEMORANDUM <br /> <br />May 9, 2014 <br />Date: <br /> <br />Amy Colby amyc@jpcarchitects.com; Carrie Walker <br />To: <br /> <br />carriew@jpcarchitects.com, Scott Thompson <br />scott@scottathompson.com. <br /> <br />John Westfall, Fire Marshal 425.771.0213 <br />From: <br /> <br />Subject:BLD 2014-0357 SHERWIN-WILLIAMS WESTGATE <br /> <br />TH <br />22804 100 AVE W. <br /> <br />The Fire Department provides the following comments and corrections in accordance with the 2012 <br />International Fire Code and Edmonds Community Development Code Title 19 for existing 4810 s.f. <br />Mercantile group compartment. <br /> <br />1. Sheet 1-0.0 Deferred submittals omit FIRE ALARM SYSTEM and FIRE SPRINKLER <br />SYSTEM unless voluntary systems are desired. <br /> <br />2. Sheet 1-0.0 Note: INTENT IS TO MAINTAIN TENANT SPACE AS MERCANTILE <br />OCCUPANCY GROUP WITHIN LIMITS OF SINGLE NONSPRINKLERED CONTROL AREA <br />FOR FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE. INVENTORY OF CLASS IB, IC, II, <br />AND IIIA WILL VARY DAY TO DAY, NEVER IN EXCESS OF 1,600 GALLONS LIMIT FOR <br />NONSPRINKLERED SPACE PER 2012 IFC TABLE 5704.3.4.1. or other approved wording. <br /> <br />3. Submit letter with application from Robert Sommers, Senior Project Engineer for Sherwin <br />Williams, dated February 7, 2014, attached in this email. <br /> <br />4. Sheet I-3.1 Label space with exterior access @ NW corner of project. <br /> <br />5. Sheet I-3.1 Provide minimum rated 2A:20B:C portable fire extinguisher (typical) for <br />ordinary (moderate) Class B hazard. <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br />City of Edmonds Office of Fire Marshal <br />